VENTING ARRANGEMENTS
FOR HORIZONTAL TERMINATIONS
The diagram shows all allowable combinations of vertical runs with
horizontal terminations, using one 90
elbow).
•
Maintain clearances to combustibles as listed in "Clearances" section
•
Horizontal vent must be supported every 3 feet.
•
Firestops are required at each floor level and whenever passing
through a wall.
•
A wall thimble is mandatory for all horizontal terminations due to
high temperatures.
0
2
4
18
16
Restrictor 1-1/2" Open
14
12
Restrictor 2-1/2" Open
Set 2
10
8
6
4
47-1/2"
(1207mm)
2
Minimum
Height
Requirement
0
Gas Fireplaces
(two 45
elbows equal one 90
o
o
Horizontal (Feet)
6
8
10
12
Set 3
Restrictor 3-1/2" Open
Set 1
FOR VERTICAL TERMINATIONS
The shaded area in the diagram shows all allowable combinations of
straight vertical and offset to vertical terminations, using two 90
o
with Rigid Pipe Venting Systems for Propane and Natural Gas. Two
45
elbows equal to one 90
o
•
Vent must be supported at offsets.
•
Firestops are required at each floor level and whenever passing
through a wall.
•
Maintain clearances to combustibles as listed in the "Clearances"
section.
•
Refer to the "Vent Restrictor Position" section for details on how to
change the vent restrictor from the factory setting to 3-1/2" opening,
2-1/2"opening and to 1-1/2" opening.
Note: Must use Rigid Pipe Adaptor (770-994) when using rigid pipe.
14
16
18
20
B41XTCE-11 Gas Fireplace
elbow. Maximum of four 45
o
0
2
4
6
40
38
36
34
32
30
28
26
Restrictor 1-1/2" Open
Set 3
24
22
20
Restrictor 2-1/2" Open
18
Set 2
16
14
12
Restrictor 3-1/2" Open
10
Set 1
8
Maximum 10' Centerline to Centerline
6
4
2
0
Maximum 8' Centerline to Centerline
elbows,
o
elbows allowed.
o
Horizontal (Feet)
10
12
8