Fig. 7-13:
Safety transformer according to EN 60742
Interfering AC voltage components such as resulting from an uncontrolled
3-phase current bridge connection without smoothing with a ripple factor
(see DIN 40110/10.75, section 1.2) of 5 % are permissible.
It follows from the above that as upper voltage limit the greatest absolute
value is 30.2 V and as lower voltage limit the lowest absolute value is
18.5 V.
1,05 x 28,8 V = 30,2 V
Upper limit
28,8 V
0,866 x 30,2 V = 26,1 V
1,05 x 20,4 V = 21,4 V
Lower limit
20,4 V
0,866 x 21,4 V = 18,5 V

Fig. 7-14: Illustration of the limit values for the 24 VDC voltage

L1
L3
L2
0V
30 el
cos (30 ) = 0.866