Advertisement

Configuring the MT8001
5.4.2
Defining event behaviour – Approvals tabs
5.4.2.1 Approvals and intrusion options – Duress Alarms
ULC
2
For more information on PIZ-specific features, please contact the Customer Support Centre.
38
Building Technologies
Fire Safety & Security Products
Fig. 37
MT8001 Options tab
Configure the Approvals-1 tab (see Fig. 38) if specific EN54 or ULC Approvals are
required for the MT8001 Management Terminal
AND/OR
if you need to configure a Duress Alarm on the MT8001.
MT8001 Approvals 1 tab
Approvals
Disable event duplication
2
PIZ Approvals
EN54 Approvals
ULC Approvals
Intrusion Options – Duress Alarm
Duress Alarm transmission
Duress events suppression time
Intrusion Options – Terminal access
Key switch enabled
Intrusion Options – Resetting of Sabotage
Alarms
Sabotage Reset enabled
Configuration options
Select if you want a duplicate event from the
same point to override the primary event and
display only one event in the Event list instead
of two.
Not available
Select if EN54 Approvals are required
Select if ULC Approvals are required
Select to enable a Duress Alarm
Duress feedback delay (in seconds) before the
Duress Alarm appears on the MT8001
Default: 300 seconds
ULC applications: This box must be checked
Other applications: Optional
Enable the Reset button after a Sabotage event
048_DMS_MT8001_ICC_MP4.20_A6V10096181_a_en.doc