5.4.2.2 Intrusion options – PIN code violations
Building Technologies
Fire Safety & Security Products
Configure the Approvals-2 tab (see Fig. 39) to define a PIN code violation Alarm on
the MT8001.
To configure a PIN code violation Alarm, do the following:
1. Check the PIN code violation Alarm to enable a local Alarm on the MT8001.
2. Modify the User lockout time (in seconds), if desired.
Note: During this time, additional logins are prevented.
3. Check the PIN code Alarm transmission to enable remote transmission of the
Alarm.
4. Drag and drop the appropriate node from the Composer tree to the Approvals-2
tab window.
Note: Typically, the node will be a point on an intrusion panel.
5. In the Drop Point dialog box, do the following:
a. Choose a property from the Property drop-down list.
b. Choose a command from the Command drop-down list.
c. Change the timeout (command feedback), if desired.
6. Select Add.
Note: To update the list in the Drag and Drop window, select the node, and then
select Change or Remove.
Fig. 39
Approvals-2 tab
048_DMS_MT8001_ICC_MP4.20_A6V10096181_a_en.doc
Configuring the MT8001
41
06.2009