Configuring the MT8001

5.4.13 Setting event limits

56
Building Technologies
Fire Safety & Security Products
Fig. 49
Setting display and horn modes
A
Select when Display mode: Normal (always enabled) or User enabled (enabled only
when a user is logged on).
B
Select which buzzer / horn will sound when an alarm occurs.
C
Select when the buzzer / horn is activated (buzzer mode).
Set maximum events in the event list
In the MT8001
Event server node, set the maximum number of events that can
be on the event list at any one time. The default value is 150: during the commis-
sioning phase (when many faults may be present) a value of 300 is recommended
(max. value is 600).
Set maximum events in the history browser
In the MT8001
History browser node tab, set the maximum number of events
that can be archived in the 'Max Archived Events' field. Default value is set to 600
events (max. value is 1000).
048_DMS_MT8001_ICC_MP4.20_A6V10096181_a_en.doc
06.2009