5.4

Customising the behaviour of the MT8001

5.4.1
Defining event behaviour – Options tab
Building Technologies
Fire Safety & Security Products
Both these bitmap images should be copied in '<project folder>\XMLData\Bitmaps'
and then linked in the MT8001 options tab (see Fig. 37 on page 38, 'Framework
Options').
Item
Width in Pixels
Background
640
This section contains several subsections that tell you how to customise or tailor
the MT8001 behaviour for a facility.
How the terminal will respond to the end user is defined primarily in the Options tab
of the MT8001 node (see Fig. 37). The following list contains settings for a typical
system.
MT8001 Options tab
Mandatory login
Enable logout timeout
Logout Timeout (inactivity, in sec.)
Quiet Window Background Bitmap
Alarm Window Background Bitmap
Page after (event) selection: Instructions, Map,
Protocol, or Report.
(Event) Ordering Mode: Priority or Category
First Event Page
Event Grouping by Discipline
Fast treatment
Automatic event closing (upon reset)
Automatic event removal (upon reset)
Automatic event acknowledge (upon selection)
History file enabled
First History Page: Protocol or Report
Event Logging
Diagnostic Logging
Keep existing local user database during download
Remote transmission alarm output
Height in Pixels
Colour depth
480
256
Typical settings
Not selected
Selected
900
Bitmap defined by Client or default: Quiet.bmp
Bitmap defined by Client or left blank
2 – Instruction page
0 – Priority
0 – Alarm background
Not selected
Selected
Selected
Selected
Selected
Selected
4 – Protocol
Selected
Not selected
Not selected
Not selected
048_DMS_MT8001_ICC_MP4.20_A6V10096181_a_en.doc
Configuring the MT8001
37
06.2009