Commissioning

When the hydraulic system is filled and ready for op-
eration, connect the controller to the mains.
The controller runs an initialisation phase in which
the directional pad flashes red.
When the controller is commissioned for the first
time or when it is reset (see page 32), it will run
a commissioning menu after the initialisation phase.
The commissioning menu leads the user through the
most important adjustment channels needed for op-
erating the system. For navigating in the commission-
ing menu, see page 8.
2.1

Step-by-step parameterisation

a. Running the commissioning menu
The commissioning menu is run after the first con-
nection and after every reset (see page 32). It will
request the following basic adjustments:
• Menu language
• Time
• Date
• Circulation
• Afterheating
• Disinfection
When the last item Save at the end of the commis-
sioning menu is selected, a security enquiry appears.
If the safety enquiry is confirmed, the adjustments
are saved. For further information about the com-
missioning menu see page 13.
b. Activating the main functions
Adjustments for the main functions Circulation,
Afterheating and Disinfection can be made. Main
functions that have not been activated in the com-
missioning menu can now be activated here.
Free relays can be allocated to main functions which
require a relay. The controller always suggests the nu-
merically smallest free relay.
Sensors can be allocated to more than one function.
For further information about the main functions see
page 17.
2.1.1 Overview of relay and sensor allocation
DHW heat exchange module without circula-
tion
R4/PWM
S1
primary side
secondary side
Primärseite
Sekundärseite
DHW heat exchange module with circulation
R4/PWM
S1
primary side
secondary side
Primärseite
Sekundärseite
c. Activating additional functions
Only after the required main functions have been ac-
tivated and adjusted, should the additional functions
be activated.
Any free relay can be allocated to any of the main
functions. The controller always suggests the numeri-
cally smallest free relay.
Sensors can be allocated to more than one function.
For further information about the additional func-
tions see page 28.
Relay / sensor allocation
Terminal
Description
R4 + PWM
Primary pump
S1
Store flow sensor
S2
Hot water flow sensor
VFD
Cold water sensor
S2
VFD
Flow rate sensor
Relay / sensor allocation
Terminal
Description
R2
R4 + PWM
Primary pump
R2
Circulation pump
S1
Store flow sensor
S2
Hot water flow sensor
S2
VFD
Cold water sensor
VFD
Circulation ret. sensor
Display screens
R4
T-store flow
T-HW
T-CW
Flow rate
Display screens
R4
R2
T-store flow
T-HW
T-CW
T-circ return
7