Main menu / Additional functions / Function block
Adjustment channel Description
Function block 1
Activating the function block
Relay
Relay
Thermostat a
Thermostat a
Th-a on
Switch-on temperature Thermostat a -40 ... +250 °C
Th-a off
Switch-off temperature Thermostat a -40 ... +250 °C
Sensor
Sensor thermostat a
Thermostat b
Thermostat b
Th-b on
Switch-on temperature Thermostat b -40 ... +250 °C
Th-b off
Switch-off temperature Thermostat b -40 ... +250 °C
Sensor
Sensor thermostat b
∆T function
Differential function
∆Ton
Switch-on temperature difference
∆Toff
Switch-off temperature difference
∆Tset
Set temperature difference
Min. speed
Minimum loading pump speed
Heat source sensor
Sensor source
Heat sink sensor
Sensor sink
Timer
Timer
Days of the week
Day selection
Timer
Time frame adjustment
dVon
Switch-on flow rate
Sensor dV
Flow rate sensor display
Inverted
Inverted switching option
Ref. sensor
Reference sensor allocation
Ref. relay
Reference relay option
Mode
Reference relay mode
Relay
Reference relay 1
Relay
Reference relay 2
Relay
Reference relay 3
back
30
Adjustment range / selection Factory setting
Yes, No
No
system dependent
system dependent
Yes, No
No
40 °C
45 °C
S5
S1 ... S7, VFD
Yes, No
No
40 °C
45 °C
S5
S1 ... S7, VFD
Yes, No
No
5.0 K
1.0 ... 50.0 K
3.0 K
0.5 ... 49.5 K
2.0 ... 100 K
10.0 K
30 %
30 ... 100 %
S5
S1 ... S7, VFD
S5
S1 ... S7, VFD
-
-
All days, Monday ... Sunday,
-
Continue
00:00 ... 23:59
-
1,0 ... 40,0 l/min
8,0 l/min
-
VFD
Yes, No
No
S1 ... S7, VFD
VFD
Yes, No
No
OR, AND, NOR, NAND
OR
all relays
-
all relays
-
all relays
-