5

Troubleshooting

WARNING!
Electric shock!
Upon opening the housing, live parts are exposed!
Î Always disconnect the controller from power sup-
ply before opening the housing!
The controller is protected by a fuse. The fuse holder (which also holds the spare
fuse) becomes accessible when the cover is removed. To replace the fuse, pull the
fuse holder from the base.
Directional pad flashes red.
Sensor fault. The error code !Sensor fault is
displayed instead of a temperature on the sensor
display channel.
Short circuit or line break
Disconnected temperature sensors can be checked
with an ohmmeter. Please check if the resistance
values correspond with the table.
°C °F
Ω
Pt1000
-10
14
961
-5
23
980
0
32
1000
5
41
1019
10
50
1039
15
59
1058
20
68
1078
25
77
1097
30
86
1117
35
95
1136
40
104
1155
45
113
1175
50
122
1194
°C °F
Ω
Pt1000
55
131
1213
60
140
1232
65
149
1252
70
158
1271
75
167
1290
80
176
1309
85
185
1328
90
194
1347
95
203
1366
100 212
1385
105 221
1404
110 230
1423
115 239
1442
If a malfunction occurs, a message will appear on the display of the controller.
fuse
The display is permanently off.
Press button ➄. Display illuminated?
no
Check the power supply of the controller. Is it dis-
connected?
no
The fuse of the controller could be
blown. The fuse holder (which holds
the spare fuse) becomes accessible
when the cover is removed. The
fuse can then be replaced.
yes
Controller has been in
standby, everything o.k.
yes
Check the supply line and recon-
nect it.