∆T circ – circulation pipe temperature loss
Main menu / Circulation
Adjustment channel
Description
[empty]
Circulation mode selection
Temperature for the thermal
T-circ therm
circulation
∆t circ
Compensation of the tempera-
ture loss of the circulation pipe
Circ. runtime
Circulation runtime
Off-time before a new circula-
Circ. off-time
tion demand
Timer
Timer
Days of the week
Day selection
Timer
Time frame adjustment
back
The ∆T circ adjustment value can be used to com-
pensate the temperature loss in the circulation pipe.
When the switching condition for a function is ful-
fi lled at the VFD sensor (T-CW), the ∆T circ value
determines the temperature loss value that is to be
calculated into the control logic in order to ensure
that the switching condition can be met.
Adjustment range / selection
Circulation off;
Permanent + Off
Therm + Off
Demand + Off
Permanent + Therm
Permanent + Demand
Therm + Demand
15 ... 70 °C
3.0 ... 10.0 K
0 ... 600 s
0 ... 60 min
-
All days, Monday ... Sunday,
Continue
00:00 ... 23:59
Î Read the correct value for ∆T circ from the ta-
ble below.
During
thermal
T -circ therm and T -HW set are blocked against
each other by ∆TCirc + 2K in order to ensure that
the switch-off temperature T -circ therm can be
reached at the reference sensor.
During thermal disinfection, the set temperature for
the HW fl ow sensor is increased by ∆T circ for the
stabilisation phase, in order to ensure that the disin-
Factory setting
fection temperature can also be reached at the VFD.
Note:
The ∆T circ value has to be adapted to the
individual system and must thus be adjusted
Circulation off
by specialised craftsmen only.
∆T circ per 10 m copper pipe depending on the HW
fl ow temperature and for different pipe diameters
Pipe
38 °C
10 x 1 mm,
50 % insulation
5.0 K
10 x 1 mm,
100 % insulation
60 s
15 x 1 mm,
50 % insulation
10 min
15 x 1 mm,
-
100 % insulation
22 x 1 mm,
-
50 % insulation
22 x 1 mm,
-
100 % insulation
28 x 1.5 mm,
50 % insulation
28 x 1.5 mm,
100 % insulation
disinfection,
the
parameters
T -HW FL = 45°C T -HW FL = 60°C
0.2
0.3
0.2
0.3
0.3
0.4
0.2
0.3
0.3
0.5
0.2
0.4
0.3
0.5
0.3
0.4
23