3.3

Main functions

3.3.1 Hot water

In this menu, all adjustments for the DHW heating
can be made. The following parameters and functions
are available:
Emergency operation
Main menu / Hot water / Emergency op.
Adjustment channel
Description
Activation of the function
Emergency op.
Emergency speed
Pump speed for emergency operation 1.5 ... 100.0 %
Indication of the current hot water
T-HW
fl ow temperature for the offset of the
emergency speed
back
• Emergency operation
• Hot water set temperature
• Minimum hot water set temperature
• Maximum hot water set temperature
• Maximum exceedance of the hot water set
temperature
• Heat exchanger mode start
• Sliding hot water set temperature
• Heat pump mode
• Blocking protection
Adjustment range / selection Factory setting
Yes, No
-
The Emergency operation function can be used
for ensuring the DHW supply in the case of a sensor
fault. In this case, the primary pump will be perma-
nently run at the adjustable Emergency speed. For
this function, the emergency speed must be aligned
with the resulting hot water temperature. The display
channel T -HW enables this alignment directly in the
Hot water menu, as soon as the emergency opera-
tion has been activated.
Note:
If a sensor fault that inhibits DHW heat-
No
ing has occurred, activate the emergency
12.0 %
operation in the Emergency op. channel.
-
In order to ensure a quick entry to emergency oper-
ation in the case if an emergency, perform the align-
ment of the emergency speed as early as possible.
The emergency speed is also available for selection
in the R4 adjustment channel of the manual mode
menu. This way, the speed of the primary pump can
be limited for manual operation in order to ensure a
scald protection.