Hot water set temperature (T -HW set)
Main menu / Hot water / T -HW set
Adjustment channel Description
T-HW set
Hot water set temperature (T-HW set) 20 ... 75 °C
Minimum hot water set temperature
Main menu / Hot water / Set max
Adjustment channel
Description
Set min
Minimum hot water set temperature 20 ... 75 °C
Maximum hot water set temperature
Main menu / Hot water / Set max
Adjustment channel
Description
Set max
Maximum hot water set temperature 20 ... 75 °C
18
Adjustment range / selection Factory setting
60 °C
Adjustment range / selection Factory setting
20 °C
Adjustment range / selection Factory setting
60 °C
This parameter can be used for adjusting the T -HW
set temperature which is to be reached at the HW
fl ow sensor S2. The controller then determines the
pump speed of the primary pump such that the tem-
perature at the HW fl ow sensor on the secondary
side continuously keeps the required set tempera-
ture T-HW set.
This parameter determines the minimum limitation
for the adjustment of the hot water set temperature
T-HW set.
Note:
In order to prevent the hot water set tem-
perature from being adjusted too low, Set
max must be adjusted to suit the system
upon commissioning!
This parameter determines the maximum limitation
for the adjustment of the hot water set temperature.
Note:
In order to prevent the hot water set tem-
perature from being adjusted too high, Set
max must be adjusted to suit the system
upon commissioning!