Table A-3 EMC specifications
Item
Electromagnetic
interference (EMI)
Electromagnetic
susceptibility (EMS)
Table A-4 Cabinet specifications
Item
Dimensions (H x W x D)
Base dimensions (H x W x D)
Weight
Protection level
Installation mode
Maintenance mode
Cable routing
Issue 03 (2020-01-04)
Specifications
Conducted emission (CE)
Radiated emission (RE)
Harmonic
Fluctuation and flick
Electrostatic discharge (ESD)
Electrical fast transient (EFT)
Radiated susceptibility (RS)
Conducted susceptibility (CS)
Surge immunity
Voltage dips (DIP)
Specifications
1500 mm x 650 mm x 650 mm (excluding the base and the
protruding part of the door)
100 mm x 650 mm x 650 mm
< 120 kg (excluding rectifiers and batteries)
Equipment compartment: IP55
Battery compartment: IP44
On a floor
Operated and maintained from the front
Routed in and out from the bottom
Copyright © Huawei Technologies Co., Ltd.
A Technical Specifications
Class A, EN300386
Class A, EN300386
EN61000-3-12
EN61000-3-11
EN61000-4-2
Contact discharge: 6 kV (criterion B); air
discharge: 8 kV (criterion B)
IEC61000-4-4
Signal port: ± 1 kV (criterion B); AC power port:
± 2 kV (criterion B); DC power port: 2 kV
(criterion B)
EN61000-4-3
Field strength: 10 V/m (criterion A)
EN61000-4-6
Power port: 10 V; signal port: 3 V (criterion A)
IEC61000-4-5
AC and DC power ports: differential mode: ± 2
kV (criterion B); common mode: ± 4 kV
(criterion B). Signal port: differential mode: 0.5
kV (criterion B); common mode: 1 kV (criterion
B)
EN61000-4-11