Item
Specifications
Input frequency
Power factor
Total harmonic distortion (THD)
DC output
Output voltage range
Default output voltage
Output power
Regulated voltage precision
Ripple and noise
Psophometrically weighted noise
Current sharing imbalance
AC input protection
AC input overvoltage protection
threshold
AC input overvoltage recovery threshold
AC input undervoltage protection
threshold
AC input undervoltage recovery threshold When the voltage is restored to 90 V AC,
DC output
DC output overvoltage protection
protection
threshold
AC surge protection
Nominal lightning strike discharge current: 20 kA (8/20 µ s); maximum lightning strike
discharge current: 40 kA (8/20 µ s)
DC surge protection
Differential mode: 10 kA (8/20 µ s); common mode: 20 kA (8/20 µ s)
Safety and
IEC/EN60950-1
regulatory design
Mean time between
200,000 hours (at 25° C)
failures (MTBF)
Issue 03 (2020-01-04)
Copyright © Huawei Technologies Co., Ltd.
A Technical Specifications
Range: 45-66 Hz; nominal frequency:
50/60 Hz
≥ 0.99 (load ≥ 50%)
≤ 5% (load ≥ 50%)
-42 V DC to -58 V DC
-53.5 V DC
Maximum output power = Output power of
a single rectifier x Number of rectifiers
≤ ±1%
≤ 200 mVp-p
≤ 2 mV
< ± 5% (20%-100% load)
> 300 V AC
When the voltage is restored to 290 V AC,
the output resumes.
< 85 V AC
the output resumes.
-58.5 V DC to -60.5 V DC
If overvoltage occurs due to an internal
fault, the rectifier locks out.
If the external voltage is greater than
-63 V for more than 500 ms, the
rectifier locks out.