Maintenance
Check Whether
Item
Preventive
Indicators are normal.
maintenance
inspection (PMI)
Appearance
The paint or
electroplated coating
on the cabinet flakes
off or has scratches.
Grounding
The ground point
properly connects to
the ground bar in the
equipment room.

4.2 Rectifying Common Faults

4.2.1 AC Failure

Possible Causes
Measures
1.
2.
3.

4.2.2 AC Over Volt

Possible Causes
Issue 03 (2020-01-04)
Check Method
By observing.
By observing.
By observing the
grounding and
using a screwdriver
or wrench.
The AC input power cable is faulty.
The AC input circuit breaker is OFF.
The mains grid is faulty.
Check whether the AC input cable is loose. If yes, secure the AC input cable.
Check whether the AC input circuit breaker is OFF. If yes, handle the back-end circuit
failure and then switch on the circuit breaker.
Check whether the AC input voltage is lower than 50 V AC. If yes, handle the mains
grid fault.
The AC overvoltage alarm threshold is not set properly on the SMU.
The power grid is faulty.
Copyright © Huawei Technologies Co., Ltd.
Repair When
Measures
Common
circuit voltage
exceeds its
threshold.
An alarm is
generated.
The surface is
Repaint or repair
damaged or
the shell.
distorted.
The cable
Secure the ground
connecting the
point or replace the
ground point and
cable.
the ground bar in
the equipment room
is loose or
damaged.
4 Maintenance
Faults.
40