Parallel Power Extend Converter Installation – Bottom Row
To install a single power extend converter in the bottom row, refer to the procedure "Single Power Extend
Converter Installation – Bottom Row" starting on page 28.
Procedure
[ ] 1. If the power extend converter is to be installed for a newly connected load, connect the load and
load return cables for the position to be occupied by the power extend converter. At the same time,
connect the power extend converter return wire faston tab (P/N 565990) provided with the power
extend converter to the cabinet's return busbar (use the same location as the return lead to the
load). At the same time, connect the power extend converter paralleling busbar (P/N 60016097 for
paralleling two converters, P/N 545346 for paralleling three converters) ordered separately to the
distribution panel load busbars (use the same location as the load lead to the load). See Figure 22.
Torque hardware as indicated in Figure 22.
[ ] 2. If the power extend converter is to replace an existing circuit breaker in the distribution panel,
remove the circuit breaker and verify the load and return cables for the position to be occupied by
the power extend converter are wired correctly. At the same time, connect the power extend
converter return wire faston tab (P/N 565990) provided with the power extend converter to the
cabinet's return busbar (use the same location as the return lead to the load). At the same time,
connect the power extend converter paralleling busbar (P/N 60016097 for paralleling two
converters, P/N 545346 for paralleling three converters) ordered separately to the distribution panel
load busbars (use the same location as the load lead to the load). See Figure 22. Torque hardware
as indicated in Figure 22.
[ ] 3. Connect the return wire (P/N 564330) and return wire jumper (P/N 565752) provided with each
power extend converter to the power extend converter return wire faston tab (P/N 565990)
installed on the cabinet's return busbar in the step above. Do this for all power extend converters.
See Figure 23.
[ ] 4. Route the return wires (P/N 564330) down and behind the top distribution row, then connect them
to the power extend converters. See Figure 23. Orient the white square on the return wire faston
receptacle's locking tab as shown in Figure 23.