Dräger Flame 2350 Instructions For Use Manual page 17

Hide thumbs Also See for Flame 2350:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Test using the Dräger FS 1200 flame simulator
The flame simulator can be used to simulate exposure of the flame
detector to a real fire condition. The flame detector is exposed to
radiation at the required detection level. As a result, the flame detector
will generate a fire alarm signal.
NOTICE
If the flame detector is exposed to a flame simulator, both alarm relay
and auxiliary relay and 0-20 mA output are activated during the
simulation.
► Disconnect automatic extinguishing systems or any external
devices that may be activated during the testso that no fire
extinguishing measures are initiated.
To perform a test using the flame simulator:
1. Power up the system. Wait up to 60 seconds for the flame detector
to turn to normal state (status LED flashes green at 1 Hz).
2. Aim the flame simulator at the target point of the flame detector so
that the radiation emitted by the simulator is facing directly towards
the flame detector.
3. Press the button of the flame simulator once.
After a few seconds, a successful test shows the following results:
Component
Result
0-20 mA output
Turns to 20 mA for a few seconds and then
returns to 4 mA
Alarm relay
Activated for a few seconds and then returns
to Normal
1)
Activated for a few seconds and then returns
Auxiliary relay
to Normal
Fault relay
Remains active during the test
Status LED
Steadily lights red and then returns to normal
status (flashes green)
Turns to 5 Vdc for a few seconds and then
2)
Analog output
returns to 0 Vdc
1)
only available in wiring option 4 and 5
2)
only available for Dräger Flame 2370
en
Use
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Flame 2100Flame 2370

Table of Contents