This chapter is divided into two sections:
Maintenance procedures
Troubleshooting guide
Preventive maintenance is the key to a reliable, safe and efficient
system. The core of any preventive maintenance system is a list of
periodic tasks.
Following are suggestions for a monthly list and a yearly list.
Note:
The monthly list and the yearly list are an average
interval. If your environment is dirty, then the intervals may
be shorter.
1.
Test (leak test) safety shut-off valves for tightness of closure.
2.
Test air pressure switch settings by checking switch
movements against pressure settings and comparing with
actual impulse pressure.
3.
Visually check ignition cable and connectors.
4.
Inspect impulse piping for leaks.
5.
Remove, clean and inspect all the burners.
6.
Make sure that the following components are not damaged or
distorted:
the burner nozzle
the spark plugs
the flame sensors
the flame tube or combustion block
7.
If applicable, remove and clean all the orifice plates.
Eclipse ExtensoJet v2 Installation Guide No. 230, 9/17/2008