Electrical Installation
For EMC-compliant installation
Establish electrical contact between cable shield
and adjustable frequency drive enclosure by
using metal cable connectors or by using the
clamps provided on the equipment (see Figure 4.5
and Figure 4.6).
Use high-strand wire to reduce electrical
interference.
Do not use pigtails.
NOTICE!
POTENTIAL EQUALIZATION!
Risk of electrical interference, when the ground potential
between the adjustable frequency drive and the system
is different. Install equalizing cables between the system
components. Recommended cable cross-section: AWG 6