Advertisement

Commissioning
3.
Press navigation keys to scroll to parameter
group 0-0* Basic Settings and press [OK].
0.0%
Operation / Display
0-0
*
Basic Settings
0-1
Set-up Operations
*
0-2
*
LCP Display
0-3
*
LCP Custom Readout
Figure 5.3 Operation/Display
4.
Press navigation keys to scroll to 0-03 Regional
Settings and press [OK].
0.0%
Basic Settings
0-03 Regional Settings
[0] International
Figure 5.4 Basic Settings
5.
Press navigation keys to select [0] International or
[1] North America as appropriate and press [OK].
(This changes the default settings for a number
of basic parameters).
6.
Press [Main Menu] on the LCP.
7.
Press the navigation keys to scroll to
0-01 Language.
8.
Select language and press [OK].
9.
If a jumper wire is in place between control
terminals 12 and 27, leave 5-12 Terminal 27 Digital
Input at factory default. Otherwise, select No
Operation in 5-12 Terminal 27 Digital Input. For
adjustable frequency drives with an optional
bypass, no jumper wire is required between
control terminals 12 and 27.
10.
3-02 Minimum Reference.
11.
3-03 Maximum Reference.
12.
3-41 Ramp 1 Ramp-up Time.
13.
3-42 Ramp 1 Ramp-down Time.
14.
3-13 Reference Site. Linked to Hand/Auto Local
Remote.
MG20MA22
Instruction Manual
0.00A
1(1)
0-
**
0.00A
1(1)
0-0
*
Danfoss A/S © 10/2014 All rights reserved.

5.4.3 Asynchronous Motor Set-up

Enter the motor data in parameter 1-20 Motor Power [kW]
or 1-21 Motor Power [HP] to 1-25 Motor Nominal Speed. The
information can be found on the motor nameplate.
1.
1-20 Motor Power [kW] or 1-21 Motor Power [HP]
2.
1-22 Motor Voltage
3.
1-23 Motor Frequency
4.
1-24 Motor Current
5.
1-25 Motor Nominal Speed
5.4.4 PM Motor Set-up in VVC
NOTICE!
Only use permanent magnet (PM) motor with fans and
pumps.
Initial Programming Steps
1.
Activate PM motor operation 1-10 Motor
Construction, select [1] PM, non salient SPM
2.
Set 0-02 Motor Speed Unit to [0] RPM
Programming motor data
After selecting PM motor in 1-10 Motor Construction, the
PM motor-related parameters in parameter groups 1-2*
Motor Data, 1-3* Addl. Motor Data and 1-4* are active.
The necessary data can be found on the motor nameplate
and in the motor data sheet.
Program the following parameters in the listed order
1.
1-24 Motor Current
2.
1-26 Motor Cont. Rated Torque
3.
1-25 Motor Nominal Speed
4.
1-39 Motor Poles
5.
1-30 Stator Resistance (Rs)
Enter line to common stator winding resistance
(Rs). If only line-line data are available, divide the
line-line value by 2 to achieve the line to
common (starpoint) value.