Symptom
Possible cause
Resonances
Acoustic noise
or vibration
Table 7.6 Troubleshooting
MG20MA22
Instruction Manual
Test
Bypass critical frequencies by using
parameters in parameter group 4-6* Speed
Bypass.
Turn off over-modulation in 14-03 Overmo-
dulation.
Change switching pattern and frequency in
parameter group 14-0* Inverter Switching.
Increase Resonance Dampening in
1-64 Resonance Damping.
Danfoss A/S © 10/2014 All rights reserved.
Solution
Check if noise and/or vibration have been
reduced to an acceptable limit.