Danfoss VLT AQUA Drive FC 202 Instruction Manual page 70

0.25–90 kw
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
380–480 V
Enclosure
A2
A3
A4
A5
B1
B2
B3
B4
8
8
C1
C2
C3
C4
Table 8.14 380–480 V, Enclosure Types A, B and C
68
Power [kW]
Recommended
fuse size
1.5–5 [1.1–4.0]
gG-10 (0.5–4 [0.37–3])
gG-16 (5 [4])
7.5–10 [5.5–7.5]
gG-16
1.5–5 [1.1–4.0]
gG-10 (0.5–4 [0.37–3])
gG-16 (5 [4])
1.5–10 [1.1–7.5]
gG-10 (0.5–4 [0.37–3])
gG-16 (5–10 [4–7.5])
15–25 [11–18.5]
gG-40
30–40 [22–30]
gG-50 (25 [18.5])
gG-63 (30 [22])
15–25 [11–18]
gG-40
30–50 [22–37]
gG-50 (25 [18.5])
gG-63 (30 [22])
gG-80 (40 [30])
50–75 [37–55]
gG-80 (40 [30])
gG-100 (50 [37])
gG-160 (60 [45])
100–125 [75–90]
aR-200 (75 [55])
aR-250 (100 [75])
60–75 [45–55]
gG-100 (50 [37])
gG-160 (60 [45])
100–125 [75–90]
aR-200 (75 [55])
aR-250 (100 [75])
Danfoss A/S © 10/2014 All rights reserved.
®
VLT
AQUA Drive FC 202
Recommended
max. fuse
gG-25
gG-32
gG-32
gG-32
gG-80
gG-100
gG-63
gG-125
gG-160
aR-250
gG-150 (50 [37])
gG-160 (60 [45])
aR-250
Recommended circuit
Max. trip level [A]
breaker
Moeller
PKZM0-25
PKZM0-25
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
3.94 [100]
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
NZMB2-A200
NZMB2-A250
25
25
25
25
63
50
100
160
250
150
250
MG20MA22