2-6
Component Test Procedures
Table 2.B Forward Biased Diode Tests on Rectifying Module for Power Structure #2
Meter Leads
-
+
Nominal meter reading
(1)
DC+/R+
2L1
DC+/R+
2L2
DC+/R+
2L3
Meter should beep once and value
should gradually rise to about 0.5V
2L1
DC-
2L2
DC-
2L3
DC-
(1)
If the drive does not contain the brake chopper option, the DC+/R+
terminal will be labeled DC+.
Table 2.C Reverse Biased Diode Tests on Rectifying Module for Power Structure #1
Meter Leads
+
-
Nominal meter reading
1L1
DC-
1L2
DC-
1L3
DC-
Meter should display ".0L" (zero load)
(1)
DC+/R+
1L1
DC+/R+
1L2
DC+/R+
1L3
(1)
If the drive does not contain the brake chopper option, the DC+/R+
terminal will be labeled DC+.
Table 2.D Reverse Biased Diode Tests on Rectifying Module for Power Structure #2
Meter Leads
+
-
Nominal meter reading
2L1
DC-
2L2
DC-
2L3
DC-
Meter should display ".0L" (zero load)
(1)
DC+/R+
2L1
DC+/R+
2L2
DC+/R+
2L3
(1)
If the drive does not contain the brake chopper option, the DC+/R+
terminal will be labeled DC+.
If the drive fails any of these measurements, replace the appropriate
Rectifying Module.
4. Conduct forward and reverse biased diode tests on the Output Power
Modules.
Table 2.E Forward Biased Diode Tests on Output Power Modules for Power Structure
#1
Meter Leads
+
-
Nominal meter reading
DC-
1U/T1
DC-
1V/T2
DC-
1W/T3
Meter should display ".0L" (zero load)
(1)
1U/T1
DC+/R+
1V/T2
DC+/R+
1W/T3
DC+/R+
(1)
If the drive does not contain the brake chopper option, the DC+/R+
terminal will be labeled DC+.