42
Use in Hazardous Environments
Table 16: Description of Marking Example for Approved Ex i I/O Modules According to ATEX and
IECEx
Gases
II
3(1)G
3(2)G
Ex
nA Gc
[ia Ga]
[ia Gb]
IIC
T4
Pos : 88.9 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
750-517 2DO 230V AC 1.0A/ Relay 2CO/ Potential Free
Equipment group: All except mining
Category 3 (Zone 2) equipment containing a safety
device for a category 1 (Zone 0) equipment
Category 3 (Zone 2) equipment containing a safety
device for a category 2 (Zone 1) equipment
Explosion protection mark
Type of protection and equipment protection level
(EPL): Non-sparking equipment
Type of protection and equipment protection level
(EPL): associated apparatus with intrinsic safety
circuits for use in Zone 0
Type of protection and equipment protection level
(EPL): associated apparatus with intrinsic safety
circuits for use in Zone 1
Explosion group of gas and vapours
Temperature class: Max. surface temperature 135°C