WAGO-I/O-SYSTEM 750
750-517 2DO 230V AC 1.0A/ Relay 2CO/ Potential Free
Pos : 84 /Serie 750 ( WAGO-I/O-SYST EM)/Ans chli eßen/Anschl uss beispi ele/Digitalausgangs klemmen/Ansc hl ussbeis piel e 750-0517_getrennte_Stromkr eise + Rei hensc haltung @ 23\mod_1440683248412_21.doc x @ 190457 @ 33 @ 1
6.2.3
Operating the Relay in Separate Current Circuits
Figure 13: Connection Example ‒ Separate Current Circuits
In this connection example, the I/O module operates in two separate current
circuits. In current circuit I (DC), channel 1 acts as a break contact. In current
circuit II (AC), channel 2 acts as a main contact. In this way, the following logical
function is realized:
• OUT_I = /DO1
• OUT_II = DO2
Manual
Version 1.1.2
Connect Devices
33