Calenta 25s - 28c - 35s - 40c
7.4
Specific maintenance operations
2
1
040412 - 7600585-01
If the standard inspection and maintenance operations have revealed
the necessity to carry out additional maintenance work, proceed as
follows, depending on the nature of the work:
7.4.1.
Replace the ionization/ignition electrode in the following cases:
4 Ionization current <3 µA.
4 Electrode worn.
4 Electrode available in the maintenance kit.
If replacement is necessary, proceed as follows:
1. Remove the cable from the ionization/ignition electrode on the
3
ignition transformer.
2. Unscrew the 2 screws and remove the ionization/ignition
electrode.
3. Replace the ionization/ignition electrode.
T001528-A
7.4.2.
Depending on the water quality and the operating mode, limescale
deposits may form in the plate exchanger and the water filter
cartridge. Periodic descaling may therefore be necessary. As a
general rule, a periodic inspection, along with cleaning, if necessary,
is sufficient. The following factors may affect the periodicity:
4 Water hardness.
4 Composition of the limescale.
4 Number of hours' operation of the boiler.
4 Draw-off rate.
4 Domestic hot water set point temperature.
CAUTION
After maintenance operations, fill in the corresponding
checklist in the maintenance log provided .
Replacing the ionization/ignition electrode
Cleaning the plate exchanger (domestic hot
water end) and the water filter cartridge
7. Checking and maintenance
79