2. Commissioning
2−36
System start" parameter
With the system parameter System start" you can influence
the starting reaction. If possible select the setting System
start with default parametrizing and current CPX system
equipment."
If the M LED lights up permanently after the system start,
then System start with saved parametrizing and saved CPX
system equipment" is set.
Caution
With CPX terminals, on which the M LED lights up perma
nently due to the parameter setting System start with
saved parametrizing and saved CPX system equipment,"
modifications to the parametrizing have been undertaken.
In these cases, check before replacement to see which
settings are required and carry out these settings.
Festo P.BE−CPX−FB23−EN en 0308NH