Siemens SIMATIC NET System Manual page 357

Industrial ethernet / profinet industrial ethernet
Hide thumbs Also See for SIMATIC NET:
Table of Contents

Advertisement

● Configuration via STEP 7 TIA Portal as of V14 SP1 or higher
● Supported controllers: S7-1200, S7-1500, ET 200SP, OpenController
Features
Connection PROFINET/Industrial Ethernet
Connection BACnet/IP
Transmission rate - Industrial Ethernet
Power supply
Integrated 2-port real-time switch
Diagnostic LEDs
C-PLUG slot
● Suitable / available or according to the specified standard.
Functions
● PROFINET IO
● Operation as "BACnet Client" or "BACnet Server"
The functionality is specified during configuration, mixed operation of client and server
functionality possible.
● Data transmission:
– Acyclic (programmed from the automation program); via the "Data record read/write"
– Cyclic (can be parameterized in HSP by the user); via updating of the IO image
– At change of value via Change of Value (COV) mechanism
● Scan of the BACnet/IP network
● Supported BACnet object types:
– Device
– Binary input / binary output
– Analog input / analog output
Supported BACnet services:
– DS-COV-A/B
– DM-DDB-A/B
– DM-DOB-B
– DS-RP-A/BDS-WP-A/P
– GW-EO-B
Industrial Ethernet
System Manual, 09/2019, C79000-G8976-C242-10
services
10.3 PN/BACnet Link Gateway
SIMATIC PN/BACnet link
2x RJ45
1x RJ45
Max. 100 Mbps
24 V DC
Gateways
357