Alarm Display
Digital
RUN
ALARM
(Green)
(Red)
Operator
108
All manuals and user guides at all-guides.com
Inverter
Explanation
Status
OH (Cooling fin overheat)
Temperature rise because of
inverter overload operation or
intake air temperature rise.
Protective
Operation
OL1 (Motor overload)
Output is shut
Motor overload protection
OFF and motor
operates by built-in electronic
coasts to a
thermal overload relay.
stop.
OL2 (Inverter overload)
Inverter overload protection
operates by built-in electronic
thermal overload relay.
OL3 (Over torque detection)
Inverter output current
exceeded the preset value in
parameter n60.
When over torque is detected,
inverter performs operation
according to the preset setting
of parameter n59.
Causes and
Corrective Actions
• Excessive load
• Improper V/f pattern
setting
• Insufficient axel time
if the fault occurs
during acceleration.
• Intake air
temperature
exceeding 122°F
(50°C)
• Calling fan stops
Check the following:
• Load size
• V/f pattern setting
(parameters n11 to
n17)
• Intake air
temperature
• Check the load size
or V/f pattern setting
(parameters n09 to
n15)
• Set the motor rated
current shown on the
nameplate by
parameter n36.
• Check the load size
or V/f pattern setting
(parameters n09 to
n15)
• Check the inverter
capacity.
Check the driven
machine and correct
the cause of the fault,
or increase the value of
parameter n60 up to
the highest value
allowed for the
machine.