Figure 3-24: Test Modes - Configuring Exerciser 1 For A Daily Exercise; Figure 3-25: Test Modes - Configuring Exerciser 2 For A Weekly Exercise; Figure 3-26: Test Modes - Configuring Exerciser 3 For A 14-Day Exercise - Woodward DTSC-200 Configuration Manual

Ats controller
Hide thumbs Also See for DTSC-200:
Table of Contents

Advertisement

Manual 37483C
Example 1: Daily Exerciser
The following configuration example shows how to configure "Exerciser 1" for a daily "No Load Test" at 14:30
(2:30 pm), which shall last 1 hours and 40 minutes.
Example 2: Weekly Exerciser
The following configuration example shows how to configure "Exerciser 2" for a weekly "Load Test" every
Wednesday at 12:00 (noon), which shall last 0 hours and 30 minutes.
Example 3: 14-Day Exerciser
The following configuration example shows how to configure "Exerciser 3" for a "Load Test" every 14 days at
18:45 (6:45 pm), which shall last 2 hours and 45 minutes, starting on October 12, 2008. The next test would take
place on October 26, 2008, i.e. 14 days later.
* N/A means that this setting is not important for the respective Exerciser Type
Page 64/158
ID
Parameter
6490
Exerciser Type
6491
Exerciser start time hour
6492
Exerciser start time minute
6493
Exerciser start day of week
6494
Exerciser start day
6495
Exerciser start month
6499
Exerciser start year
6496
Exerciser duration hours
6497
Exerciser duration minutes
6498
Exerciser test type

Figure 3-24: Test modes - configuring exerciser 1 for a daily exercise

ID
Parameter
6503
Exerciser Type
6504
Exerciser start time hour
6505
Exerciser start time minute
6506
Exerciser start day of week
6507
Exerciser start day
6508
Exerciser start month
6512
Exerciser start year
6509
Exerciser duration hours
6510
Exerciser duration minutes
6511
Exerciser test type

Figure 3-25: Test modes - configuring exerciser 2 for a weekly exercise

ID
Parameter
6516
Exerciser Type
6517
Exerciser start time hour
6518
Exerciser start time minute
6519
Exerciser start day of week
6520
Exerciser start day
6521
Exerciser start month
6525
Exerciser start year
6522
Exerciser duration hours
6523
Exerciser duration minutes
6524
Exerciser test type

Figure 3-26: Test modes - configuring exerciser 3 for a 14-day exercise

DTSC-200 - ATS Controller
Setting
Daily
14 h
30 min
N/A *
N/A *
N/A *
N/A *
1 h
40 min
No Load
Setting
Weekly
12 h
00 min
3 (Wednesday)
N/A *
N/A *
N/A *
0 h
30 min
Load
Setting
14-Day
18 h
45 min
N/A *
12
10
08
2 h
45 min
Load
© Woodward