Page 1
37443A DSLC-2 Digital Synchronizer and Load Control Manual Software Version 1.14xx Manual 37443A...
Page 2
Provides other helpful information that does not fall under the warning or caution categories. Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be correct and reliable. However, Woodward assumes no responsibility unless otherwise expressly undertaken.
• 11-05-13 Minor corrections New features Requirements: Digital synchronizer and load control (DSLC-2)with software revision 1.1404 or higher and device revision A or higher. • Modbus communication: Loss of connection. Refer to “Loss Of Connection” on page 192 for details.
Page 4
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Menu (Setpoint) Description ........................57 DSLC-2 – Homepage ........................57 Menu 1 – Synchronizer ....................... 61 Menu 2 – Load Control ........................ 65 Menu 3 – Process Control ......................69 Menu 4 – Var / PF Control ......................71 Menu 5 –...
Page 5
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control 5. R .............. 160 HAPTER OWER ONTROL ESCRIPTION Introduction............................160 Power Management Concepts ......................160 Droop ............................160 Droop Tracking .......................... 161 Isochronous ..........................161 Droop/Isochronous Load Sharing On An Isolated Bus .............. 162 Isochronous Load Sharing On An Isolated Bus .................
Page 6
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control A. T .................... 201 PPENDIX ECHNICAL Environmental Data ..........................203 Accuracy .............................. 204 B. U ..................205 PPENDIX SEFUL NFORMATION Connecting 24 V Relays ......................205 C. D ..................206 PPENDIX ROTOCOLS Data Protocol 5200 ..........................
Page 7
Figure 2-2: Housing - drill plan ..............................20 Figure 2-3: DSLC-2 - terminal arrangement ..........................21 Figure 2-4: Wiring diagram - DSLC-2 - 1/2 ..........................22 Figure 2-5: Wiring diagram - DSLC-2 - 2/2 ..........................23 Figure 2-6: Power supply ................................25 Figure 2-7: Power supply - crank waveform at maximum load ....................
Page 8
Figure 9-1: Diagram frequency / active power controller ....................... 182 Figure 9-2: Diagram voltage / reactive power controller ......................183 Figure 10-1: DSLC-2 - interface overview (housing - side view) ................... 184 Figure 10-2: Modbus - visualization configurations ....................... 188 Figure 10-3: Modbus - sending binary digital orders over interface ..................
Page 9
Table 3-29: Parameter – DSLC-2 overview page 1 ........................ 112 Table 3-30: Parameter – DSLC-2 overview page 2 ........................ 114 Table 3-30: Parameter – DSLC-2 overview page 3 – MSLC-2 ....................116 Table 4-1: Low voltage system 480 V / 277 V – 3-phase with neutral ................... 143 Table 4-2: Low voltage system 480 V / 277 V –...
Page 10
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Table 10-11: Modbus – generator voltage measuring ......................197 Table 10-12: Modbus – reset default values ........................... 198 Table 10-13: Modbus - serial interface 1 - parameters ......................200 Table 10-14: Modbus - serial interface 2 – parameters ......................200 Table 10-15: Modbus - TCP/IP Network B–...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Chapter 1. General Information Document Overview ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ This manual describes the Woodward DSLC-2 Digital Synchronizer and Load Control. Type English German DSLC-2 this manual DSLC-2 – User Manual 37443 MSLC-2 – User Manual...
The DSLC-2 control provides a safe automatic dead-bus closure function. Deadbus closing permission is granted to only one DSLC-2 or MSLC-2 control in the whole system, through locking techniques done over the communications network. This assures that a race condition will not cause two or more breakers to close simulta- neously on the dead bus.
Load Control ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Load control begins at breaker closure when the load control function takes control of the DSLC-2 speed bias output directly from the synchronizer. The matching of synchronizer slip frequency to initial load (unload trip level) can result in a bumpless transfer to load control. On command, the adjustable ramp allows smooth, time- controlled loading into base load, isochronous load sharing or process control.
The var/PF controller will limit the generators kvar output to the generator rated reactive power setpoint when connected to an infinite bus. A DSLC-2 must be in baseload or process control or a MSLC-2 must be in control. This will protect the generator when connected to an infinite source. This feature is not active when the DSLC-2 is in the load sharing mode (isolated).
DSLC-2 / MSLC-2 Systems ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The network addressing of the DSLC-2 / MSLC-2 allows up to 32 DSLC-2s and 16 MSLC-2s in an application. A DSLC-2 and MSLC-2 application can handle 8 segments. Discrete inputs inform the DSLC-2s and MSLC-2s which segments each generator and utilities are operating on.
CAUTION To prevent damage to electronic components caused by improper handling, read and observe the pre- cautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Printed Circuit Boards and Modules. NOTE The unit is capable to withstand an electrostatic powder coating process with a voltage of up to 85 kV and a current of up to 40 µA.
Protect the unit from direct exposure to water or to a condensation-prone environment. • The continuous operating range of the DSLC-2 control is –40 to +70 °C (–40 to +158 °F). • Provide adequate ventilation for cooling. Shield the unit from radiant heat sources.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Installation The unit is to be mounted to the switch cabinet back using four screws with a maximum diameter of 6 mm. Drill the holes according to the dimensions in Figure 2-2 (dimensions shown in mm).
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Connections ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ WARNING All technical data and ratings indicated in this chapter are not definite! Only the values indicated in Ap- pendix A. Technical Data on page 201 are valid! The following chart may be used to convert square millimeters [mm²] to AWG and vice versa: mm²...
Table 2-2: Power supply - terminal assignment Figure 2-7: Power supply - crank waveform at maximum load NOTE Woodward recommends to use one of the following slow-acting protective devices in the supply line to terminal 63: • Fuse NEOZED D01 6A or equivalent •...
DO NOT use both sets of voltage measuring inputs. The control unit will not measure voltage correctly if the 120 V and 480 V inputs are utilized simultaneously. NOTE Woodward recommends protecting the voltage measuring inputs with slow-acting fuses rated for 2 to 6 A. Voltage Measuring: Generator...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Voltage Measuring: Generator Parameter Setting '3Ph 4W OD' (3-phase, 4-wire, Open delta) A generator system that is connected to the load through a 3-phase, 4-wire connection but have the device wired for a 3-phase, 3-wire installation may have the L2 phase grounded on the secondary side.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control 3Ph 4W OD Wiring terminals Note Rated voltage (range) [1] 120 V (50 to 130 V [4] 480 V (131 to 480 V eff. eff. Measuring range (max.) [1] 0 to 150 Vac...
2W' (1-phase, 2-wire) NOTE The 1-phase, 2-wire measurement may be performed phase-neutral or phase-phase. Please note to configure and wire the DSLC-2 consistently. Refer to the chapter Configuration & Operation. '1Ph 2W' Phase-Neutral Measuring Figure 2-16: Voltage measuring - busbar measuring inputs, 1Ph 2W (phase-neutral)
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control '1Ph 2W' Phase-Phase Measuring Figure 2-17: Voltage measuring - busbar measuring inputs, 1Ph 2W (phase-phase) 1Ph 2W Wiring terminals Note Rated voltage (range) [1] 100 V (50 to 130 V [4] 400 V (131 to 480 V eff.
480 V input terminals must be used for proper measurement. NOTE If the DSLC-2 is intended to be operated in parallel with the mains, the mains voltage measuring inputs must be connected. If an external mains decoupling is performed, jumpers between busbar and aux- iliary busbar voltage measuring inputs may be installed.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Current Measuring CAUTION Before disconnecting the device, ensure that the current transformer/CT is short-circuited. Generator Current NOTE Generally, one line of the current transformers secondary is to be grounded close to the CT.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Current Measuring: Generator, Parameter Setting 'L1 L2 Gen L1 Gen L2 Gen L3 Figure 2-24: Current measuring - generator, L1 L2 L3 L1 L2 L3 Wiring terminals Notes DSLC-2 terminal Phase...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Power Measuring If the unit's current transformers are wired according to the diagram shown, the following values are displayed. Parameter Description Sign displayed Generator real power Genset generating kW + Positive...
Page 40
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Different power factor displays at the unit: i0.91 (inductive) c0.93 (capacitive) lg.91 (lagging) ld.93 (leading) Reactive power display at the unit: 70 kvar (positive) -60 kvar (negative) Output at the interface:...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Discrete Inputs Discrete Inputs: Signal Polarity The discrete inputs are electrically isolated which permits the polarity of the connections to be either positive or negative. NOTE All discrete inputs must use the same polarity, either positive or negative signals, due to the common ground.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Relay Outputs Figure 2-29: Relay outputs Terminal Description Term. Com. Type Form A, N.O. make contact Relay output [R 01] {all} Alarm (Self Test OK) N.O. 2.5 mm² Relay output [R 02]...
Page 44
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Alarm Load High Breaker Breaker Centr. Alarm 1 Alarm 2 Alarm 3 Voltage Voltage Switch Limit Limit Open Close Alarm Raise Lower Self Test Load switch alarm Reverse power High load limit...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Analog Inputs The following senders may be used for the analog inputs: • 0 to 20mA • 4 to 20mA • 0 to 10V • 0 to 5V • 1 to 5V...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Analog Outputs Controller speed and voltage bias output signals. Jumper configuration will change the function for a voltage output signal. Configuration for the speed and voltage bias outputs is done in Menu 6.2.
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Install ToolKit Configuration And Visualization Software NOTE Woodward’s ToolKit software is required to configure the unit via PC. ToolKit Version 3.6.0 or higher Install ToolKit Software Please insert the enclosed Product CD in the CD-ROM drive of your computer The CD is going to start automatically (autostart function needs to be activated) Please go to the section “Software”...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Install ToolKit Configuration Files Please insert the enclosed Product CD in the CD-ROM drive of your computer The CD is going to start automatically (autostart function needs to be activated) Please go to the section “Configuration Files” and follow the instructions described there Alternatively ToolKit configuration files can be downloaded from our Website.
DSLC-2 - Digital Synchronizer and Load Control Starting ToolKit Software Start ToolKit via Windows Start menu -> Programs ->Woodward -> ToolKit 3.x Please press the button “Open Tool” Go to the “Application” folder and open then the folder equal to the part number (P/N) of your device (e.g.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Configure ToolKit Software Start the configuration by using the toolbar. Please go to Tools -> Options The options window will be displayed Adjust the default locations of the configuration files The displayed language can be selected here The changes become effective after clicking “OK”...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control View DSLC-2 Data With ToolKit The following figure shows an example visualization screen of ToolKit: Figure 3-1: ToolKit - visualization screen Navigation through the various visualization and configuration screens is performed by clicking on icons, by selecting a navigation button (e.g.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Configure The DSLC-2 With ToolKit The following figure shows an example configuration screen of ToolKit: Figure 3-3: ToolKit - configuration screen Entering a new value or selecting a value from a defined list will change the value in a field. The new value is written to the controller memory by changing to a new field or pressing the Enter key.
This parameter identification number is also displayed in the ToolKit configuration screens next to the respective parameter. DSLC-2 – Homepage This is the basic page of the DSLC-2. It gives general information, such as: • The generator condition •...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control General Parameter Setting range Format Description 4602 Synchronizer Off / Display of the different Synchronizer modes: mode Synchronized / Permissive / Off: The synchronizer is not active. Check / Synchronized: The GCB is closed.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Format Description 4605 Process Info 0.0 % Indicates the Process reference value in percentage. reference 7726 Process Info 0.0 kW Indicates the Process reference value in engineering units.
The parameter Dead bus detection max. volt. (parameter 5820) defines the dead bus condition. Figure 3-8: ToolKit - home page - segments This figure indicates which segments in the DSLC-2 / MSLC-2 system are interconnected. LED: Missing device – Indicates that the configured number of connected members (DSLC-2 and MSLC-2) is not recognized on the network.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Menu 1 – Synchronizer This menu contains the adjustments of the synchronizer. Figure 3-9: ToolKit – synchronizer PID Frequency Control Parameter Setting range Default Description 4539 Frequency 0.01 to 100.00 1.00...
70.00 Hz tor frequency has exceeded the value configured in this parame- trol level ter. This prevents the DSLC-2 from attempting to control the fre- quency while the engine is completing its start sequence. 5517 Start 0 to 999 s...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Synchronizer Control Parameter Setting range Default Description 5729 Synchroniza- Slip frequency./. Phase Slip frequency: The synchronizer adjusts the generator frequen- tion GCB Phase matching matching cy to a point greater than the busbar. The slip frequency is deter- mined by the setting of Slip frequency setpoint offset (parameter 5502).
If the “CB Aux” contact opens during the reclose delay interval, it is considered a failed closed attempt. The DSLC-2 control will re- main in the selected operating mode (run, check or permissive) during the reclose delay interval.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Menu 2 – Load Control This menu contains the adjustments for load control. Figure 3-11: ToolKit – load control PID Frequency Trimmer Parameter Setting range Default Description 5510 Frequency 0.01 to 100.00 0.50...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Default Description 5512 Frequency 0.01 to 100.00 0.01 The derivative ratio identifies the “D” part of the PID controller. By trim deriva- decreasing this parameter, the stability of the system is increased.
0.5 to 99.9 % 3.0 % The percentage load level where the breaker open command is level given when the DSLC-2 is in the “Unload” mode. NOTE: This value refers to the generator rated active power (parameter 1752). 3123 Unload trip...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Default Description 4549 Load ramp 0.01 to 3.00 %/s The Load ramp rate is valid when loading the generator. rate 100.00 %/s NOTE: This value refers to the generator rated active power (parameter 1752).
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Menu 3 – Process Control This menu contains the adjustments for process control. Figure 3-13: ToolKit – process control PID Process Control Parameter Setting range Default Description 4500 Process 0.01 to 100.00 2.00...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Process Control Parameter Setting range Default Description 4508 Process 0.0 to 100.0 % 0.0 % The Process droop is the load droop desired based on process droop level. 4509 Process filter...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Menu 4 – Var / PF Control This menu contains the adjustments for reactive load control. Figure 3-15: ToolKit – var / pf control PID Voltage Trimmer Parameter Setting range Default...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Default Description 5612 Voltage trim 0.01 to 100.00 0.01 The derivative ratio identifies the “D” part of the PID controller. By derivative decreasing this parameter, the stability of the system is increased.
5604 Reactive 0.0 to 20.0 % 0.0 % Woodward recommends having around 3 % droop in the voltage load droop regulator. Reactive load droop is not needed when the voltage regulator has droop. Reactive load droop must be added if the vol- tage regulator does not have droop.
999999.9 kvar kvar used as a reference figure for related functions. The DSLC-2 limits the var output from -10 to 100 % of the rated setting when in base load mode, process mode and with an active MSLC-2.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Voltage Monitoring Parameter Setting range Default Description 1770 Generator Phase - phase / Phase - This configuration determines the monitored voltage type. voltage Phase - neutral phase monitoring Phase – phase: Only the phase - phase voltages VL12, VL23 and VL31 are monitored.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control 3pos Controller Reactive Power Parameter Setting range Default Description 5660 Reactive 0.001 to 0.300 0.010 This configures a deadband around the power factor reference power value. The generator power factor is controlled in such a manner,...
21-28 can additionally be used. When both measurements are used the busbar voltage has to be connected to both inputs. With the parallel use of the auxiliary busbar measurement, the DSLC-2 can determine correct voltages on all 3 phases on the bus and becomes part of the operating range- and the phase rotation monitoring.
This measurement can be directly connected or through potential transformers (PTs). Voltage monitoring is configured in the “VAR/PF Menu 4”, parameter 1770. This setting determines if the DSLC-2 uses “Phase - phase” or “Phase - neutral” voltage for pro- tection. 3Ph 3W: Delta connected voltages Generator voltage is connected using all 3 phases.
This measurement can be directly connected or through potential transformers (PTs). Voltage monitoring is configured in the “VAR/PF Menu 4”, parameter 1770. This settings determines if the DSLC-2 uses “Phase - phase” or “Phase - neutral” voltage for pro- tection. 3Ph 3W: Delta connected voltages Generator voltage is connected using all 3 phases.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Transformer Parameter Setting range Default Description 1801 Gen. PT 50 to 650000 V 480 V The value is always entered as the “Phase - phase” measure- primary ment. Some generator applications may require the use of poten-...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Default Description 1803 Bus PT 50 to 480 V 120 V The value is always entered as the “Phase - phase” measure- secondary ment. Some applications may require the use of potential trans- rated volt.
1 to 8 The Basic segment number describes where the DSLC-2 is segment placed in relation to other DSLC-2 or MSLC-2. As long as no tie- number breaker is located between the busbar voltage measurement of multiple DSLC-2s, the parameter can remain on “1”.
The serial interface 1 – RS-232 is mainly used for the configuration tool, ToolKit. This is executed with the Woodward own Servlink protocol. The RS-232 also allows access by Modbus protocol with fixed parity, stop bits and full-, halfduplex mode. The unit acts here as a RTU slave.
Network B – Modbus/TCP The network B – Modbus/TCP Ethernet bus is provided for external communication purposes between all DSLC-2 / MSLC-2 in one system and a PLC. Up to 10 TCP/IP stacks can be built up per unit. Parameter...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Modbus Interface Definitions The unit offers a Modbus address table with for visualizing systems. The table contains 16 bit integer (short) and 32 bit integer (long) variables. The contents of some measurement long variables are also available as short va- riables.
Figure 3-21: ToolKit – system management Password System The DSLC-2 utilizes a password protected multi-level configuration access hierarchy. This permits varying de- grees of access to the parameters being granted by assigning unique passwords to designated personnel. A dis- tinction is made between the access levels as follows:...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Code level CL2 (Temporary Commissioning Level) No standard password available This code level grants temporary access to most of the parameters. The password is calculated from the random number generated when the password is initially accessed. It is designed to grant a user a one-time access to a pa- rameter without having to provide a reusable password.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Factory Settings Parameter Setting range Default Description 10417 Factory No / Yes Selecting “Yes” will allow the reset back to Factory default settings default by selecting “Yes” for the Reset factory default values parameter settings (parameter 1701).
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Remote Load Reference Input / Process Reference Input This analog input can be used for two functionalities: Remote load reference (baseload) input. The input becomes active, if the DI “Load Raise”/”Load Low- er”...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Linear Parameter Setting range Default Description 4311 User defined -100.0 to 0.0 % Remote load reference input / process reference input. Linear min display 100.0 % scaling: This is the percentage value according to the lowest value hardware signal.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Linear Parameter Setting range Default Description 4322 User defined -100.0 to 0.0 % Process signal input (real value). Linear scaling: This is the per- min display 100.0 % centage value according to the lowest hardware signal.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Linear Parameter Setting range Default Description 4333 User defined -0.999 to -0.710 PF Power factor reference signal input. Linear scaling: This is the min display 0.999 PF power factor value according to the lowest hardware signal.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Speed Bias Output The hardware of the speed bias output is able to drive signals between +/-20mA. Out of this range different sig- nals can be created. The switching from a current output to a voltage output is achieved by adding a jumper be- tween terminals 15 and 16.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Default Description 5203 Filter time Off / 1 to 7 A filter time constant may be used to reduce the fluctuation of an constant analog output reading. This filter time constant assesses the av- erage of the signal according to the following formula: −...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Voltage Bias Output Parameter Setting range Default Description 5215 Selected select from list 0 to 20mA This parameter is used to configure the appropriate type of analog hardware below / 0 to 10V controller signal.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control User defined (Hardware range) Parameter Setting range Default Description 5222 User defined 0 to 100 % 0.00 % The minimum output value, which shall correspond with the mini- min. output mum value of the output range, must be entered here. This para- value meter is only active, if parameter 5215 is configured to "user de-...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Menu 7 – Electrical Parameters This menu contains the electrical parameters of the DSLC-2. Only shown, if auxiliary busbar is enabled (parameter 7629) Figure 3-31: ToolKit – electrical parameters Menu 7 provides all the AC measurement, voltage, current, power and reactive power. The generator is always a 3-phase measurement and the busbar is measured as a single phase.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Format Description Generator Info 1.00 Display of Generator power factor L1. power factor Generator Info 1.00 Display of Generator power factor L2. power factor Generator Info 1.00 Display of Generator power factor L3.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Auxiliary Busbar Measurement Parameter Setting range Format Description Aux busbar Info 0.0 V Display of Auxiliary busbar voltage L1-N in V. voltage L1-N Aux busbar Info 0.0 V Display of Auxiliary busbar voltage L2-N in V.
DSLC-2 - Digital Synchronizer and Load Control Menu 8 – Control Status Monitor This menu contains the parameters of the control status monitor of the DSLC-2 showing the actual modes, refer- ences and alarms. Figure 3-33: ToolKit – control status monitor...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Format Description 7710 Reactive Off / Display of the different Reactive load control modes: load control Inactive / mode Droop / Off: The reactive load control mode is disabled.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Format Description 4617 Missing Info - / Alarm Display of Alarm: Missing loadshare member. member 4618 Centralized Info - / Alarm Display of Alarm: Centralized alarm. alarm 4619 GCB open...
Menu 9 – Discrete Inputs / Relay Outputs This menu contains the parameters for the discrete inputs, the discrete input source (hardware or communication interface) and the discrete outputs (relays) of the DSLC-2. Figure 3-35: ToolKit – discrete inputs / relay outputs...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Default Description 7709 Ramp pause Open / Closed Open Display of discrete input state for [DI 09]: Ramp pause. switch 7709 Load raise Open / Closed Open Display of discrete input state for [DI 10]: Load raise...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Default Description 4157 Source DI / COM Indicates the source of ramp pause switch either DI or communi- Ramp pause cation interface. switch 4157 Source-Load DI / COM...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Menu 0 – Diagnostics This menu contains the alarms that can be connected to output either for relays 8, 9 or 10. Figure 3-37: ToolKit – diagnostics Set Alarm to Off / Alarm1 / Alarm2 / Alarm3 Each alarm can be set on relay 8 (Alarm 1), relay 9 (Alarm 2) or relay 10 (Alarm 3).
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Default Description 7591 High voltage Off / Alarm1 / Passing the alarm to relay Alarm 1, Alarm 2 or Alarm 3. limit alarm Alarm2 / Alarm3 7592 Voltage Off / Alarm1 / Passing the alarm to relay Alarm 1, Alarm 2 or Alarm 3.
16 MSLC-2. DSLC-2 Overview Page 1 The DSLC-2 overview page 1 informs about the conditions of the DSLC-2 number 1 to 16 connected to the net- work. This helps for commissioning a DSLC-2 / MSLC-2 system. Figure 3-39: ToolKit – DSLC-2 overview page 1...
DSLC-2 - Digital Synchronizer and Load Control DSLC-2 Overview Page 2 The DSLC-2 overview page 2 informs about the conditions of the DSLC-2 number 17 to 32 connected to the network. This helps for commissioning a DSLC-2 / MSLC-2 system.
DSLC-2 - Digital Synchronizer and Load Control DSLC-2 Overview Page 3 – MSLC-2 The DSLC-2 overview page 3 informs about the conditions of the MSLC-2 number 33 to 48 connected to the network. This helps for commissioning a DSLC-2 / MSLC-2 system.
Prestart Setup Procedure ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Apply power to the DSLC-2 control. Verify that the DSLC-2 control passes its power up diagnostics by checking that self-test relay (terminal 41 / 42) is energized. If the unit fails see Appendix B. Service Options for instruc- tions on getting service for the control.
There is only one single DSLC-2 in use • There are multiple DSLC-2 / MSLC-2 installed, which work on a common bus, which cannot be sepa- rated. (only one segment available) When the application contains switching elements between DSLC-2s and/or MSLC-2s proceed with following rules: 1.
Begin on the left side with segment number 1. • The utility and the generators are not segments in sense of the DSLC-2 / MSLC-2 system. • The segment numbers have to follow a line and shall not branch. (Please refer there for to the chapter Network/System) for a better understanding.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control 6. Draw the switch and its network for Ethernet channel A and B, if used, in your online diagram (refer to Figure 3-44). Please consider following rules (for a better overview and understanding): •...
Figure 3-45). Please consider following rules (for a better overview and understanding): • The current measurement is always on system A. So the locations for the CT are fixed for DSLC-2 and MSLC-2 (only located at the utility). • MSLC-2 located at tie-breaker: When the CT at the tie-breaker is located on the right side it is allowed to turn system A and system B measurement at the tie-MSLC-2.
Set all load control (Menu 2) setpoints according to the descriptions above and the work sheet. Proportional load control mode should be used during initial setup of the DSLC-2 control. Set the unload trip setpoint to approx- imately 10 % of rated load.
The DSLC-2 has a frequency trim and voltage trim feature that is active in isochronous and load sharing modes. The DSLC-2 will be in the droop mode with no “CB Aux” feedback. Once the engine is started, the DSLC-2 will not be in any PID loop trying to control speed or voltage.
This setting will be saved as your new initial state value. 10. The adjustment of the frequency and voltage trim PIDs need the DSLC-2 in the isochronous load shar- ing mode. This is accomplished by closing the “CB Aux” input. If possible to close the generator break- er and get the true “CB Aux”...
Load Control Droop Adjustment It is important to setup the DSLC-2 control for correct kW droop operation first. This will verify correct wiring and operation of the unit in the safest possible manner. The preferred procedure uses a load bank. Only use a utility or other bus of sufficient capacity for a load if a load bank is not available.
Menu 7. If incorrect load sensor operation is observed, verify configuration values on Menu 6, phasing and other wiring connections to the DSLC-2 control. Increase the engine speed setting to increase load. When the speed bias output reaches the value required for 50 % load as measured in step 4.
Set Breaker delay (parameter 5705) to the closure time specified by the breaker manufacturer. Add de- lay time for any interposing relays if required. Set GCB close hold time (parameter 3416) to the time desired for the DSLC-2 control to hold the break- er clo-sure signal. This time should exceed the breaker delay time.
12. Open the isoch/droop switch in series with the “CB Aux” contact input to terminal 70 of the DSLC-2 control. If such a switch is not installed, temporarily remove the connection to terminal 70 to select droop mode.
Open the circuit breaker to disconnect the generator from the bus. Close the isoch/droop switch in series with the “CB Aux” contact input to terminal 70 of the DSLC-2 control. If such a switch is not installed, verify that the connection to terminal 70 is restored.
If generator voltage drops below the bus voltage and out of the voltage matching window, the DSLC-2 will provide a raise voltage relay output. If cycling above and below the voltage matching window oc- curs, adjust the 3pos controller in Menu 4.
11. Use the voltage raise input to increase generator voltage to 3 or 4 % above busbar voltage. This can be observed on the Homepage meters. 12. Place the DSLC-2 in the check mode and observe how the generator voltage is driven into the voltage matching window. To adjust the synchronizer soltage control use Menu 1.
DSLC-2 controls currently installed and powered up. NOTE It is desirable to power all DSLC-2 controls in the system and verify that all units show the correct number of active DSLC-2 controls. Duplicate Menu 5 network address setpoints, wiring errors, an over- loaded network or defective DSLC-2 controls can cause an incorrect result.
This completes the isochronous load sharing adjustments. Integrating Base Load Control Setup The DSLC-2 is an integrating base load control. A utility bus or an isolated bus with sufficient capacity is re- quired to do this setup. When in base load mode, the PID power control will be active.
Ramp the load up and down by alternately opening and closing the “Load/Unload” input. Be sure to rec- lose the switch before load drops to the unload trip level or the DSLC-2 control will issue a command to open the circuit breaker. Adjust base load proportional gain and base load integral gain to get the desired performance.
Synchronize, parallel and load the generator to the internal base load reference. Apply the analog signal to the remote load reference input of the DSLC-2 control. Adjust the remote reference to some level dif- ferent than base load or use the raise load or lower load contacts to shift the unit load to a different level.
DSLC-2s will be in process control with the same reference setting. A con- trol can be placed in the unload mode to separate from the bus, but you cannot place a DSLC-2 in base load or load sharing mode when another DSLC-2 is in process mode.
20. If it is desired that the high and low limit switches also activate the “High Limit” and “Low Limit” relay driver outputs, set the Process switches (parameter 7502) setpoint to “Enabled”. This completes setup and adjustment of the DSLC-2 process control function. Page 138/226...
Synchronizer (Menu 1) – Dead bus closure (parameter 7555) must be enabled If a missing member alarm is active (Menu 8), the DSLC-2 will not close to a dead bus i. In Menu 5, set Number of DSLC communicating (parameter 4063) to “1”...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control 17. DSLC-2 will actively synchronize and voltage match, provide a breaker closure command. 18. Load control mode will show load share ramp. 19. Reactive load control mode will show var sharing.
This section describes how generator and bus matching occurs and how all conditions are verified by the syn- chronizer functions.The examples shown in chapter “Measurement Connections (Examples)” on page 143 dem- onstrate the AC measurement connection and configuration of the DSLC-2 system. Operating Modes The operation of the synchronizer is determined by the mode switch as shown in Figure 4-1.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Measurement Connections (Examples) Low Voltage System 480 V / 277 V - 3-Phase with Neutral • Phase rotation clockwise • Generator measurement: 3-Phase with neutral • Busbar measurement : L1-L2 (“Phase – phase”) Figure 4-2: Low voltage system 480 V / 277 V –...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Low Voltage System 480 V / 277 V - 3-Phase with Neutral • Phase rotation clockwise • Generator measurement: 3-Phase with neutral • Busbar measurement : L1-N (“Phase – neutral”) Figure 4-3: Low voltage system 480 V / 277 V – 3-phase with neutral...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Low Voltage System 480 V - 3-Phase with Neutral • Phase rotation clockwise • Generator measurement: 3-Phase with neutral • Busbar measurement : L1-N (“Phase – neutral”) • Auxiliary busbar measurement: 3-Phase with neutral Figure 4-4: Low voltage system 480 V –...
Low Voltage System 600 V / 346 V - 3-Phase • Phase rotation clockwise • Generator measurement: 3-Phase PT “Open Delta” (Phase L2 (B) is grounded at the DSLC-2 connec- tion) • Busbar measurement: 1-Phase PT L1-L2 (“Phase – phase”) Figure 4-5: Low voltage system 600 V / 346 V –...
Low Voltage System 600 V / 346 V - 3-Phase • Phase rotation clockwise • Generator measurement: 3-Phase PT “Open Delta” (Phase L2 (B) is grounded at the DSLC-2 connec- tion) • Busbar measurement: 1-Phase PT L1-N (“Phase – neutral”) Figure 4-6: Low voltage system 600 V / 346 V –...
Dead Bus Closing – Multiple Units When a dead bus is detected and dead bus closing mode is “Enabled”, the DSLC-2 is doing a security check be- fore issuing a breaker closure command. This security is required to prevent two or more units from closing their breakers at the same time.
The DSLC-2 measures the RMS values of the generator and busbar voltages. The synchronizer issues appropriate raise or lower commands to the voltage regulator until the generator voltage is within the specified voltage win- dow.
The Auto re-synchronization feature (parameter 7514), when enabled, allows the DSLC-2 to attempt to reclose the breaker if the “CB Aux” feedback is opened and the DSLC-2 still has a “Run” or “Permissive” input closed. The auto re-synchronizer feature becomes active after a successful breaker closure is received. Then if the break- er feedback (CB Aux) is opened and the “Run”...
If no breaker closure is received by the end of the timer, a synchronizer timeout alarm is re- ceived and the DSLC-2 will stop the synchronizing process. If the “Run” input is removed, the alarm is reset and when the “Run”...
(lagging) reduces the voltage or an increasing capacitive load (leading) increases the voltage. The DSLC-2 in- cludes a droop setting for the voltage biasing signal. Woodward recommends that you always use a droop CT on the voltage regulator and set for around 3 % droop for best control.
Droop Tracking When an active DSLC-2 is placed in the droop tracking mode it keeps the speed and voltage bias settings at their present values. This means that the kW and kvars will remain at their present values. In the past when the control transferred into the droop mode, the generators would unload or the system frequency and voltage values may change.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Droop/Isochronous Load Sharing On An Isolated Bus Droop/isochronous combines the first two modes. All generator sets in the system except one are operated in the droop mode. The one unit not in droop is operated in the isochronous mode. It is known as the swing machine. In this mode, the droop machines will run at the frequency of the isochronous unit.
All DSLC-2 units are connected via Ethernet channel Network A. Load share is possible for all DSLC-2 units that are in the same segment. Any imbalance in load between units will cause a change to the regulating software in each unit. While each unit continues to run at isochronous speed, these changes force each machine to supply a proportional share of power to meet the total load demand on the system.
In single unit operation, speed will decrease as load increases, as described above. In parallel with a bus, the generator is loaded by increasing the speed reference. The DSLC-2 control will provide the droop signal required for stability. When the “CB Aux” contact input is closed, the generator is paralleled to a bus, the load control operating mode contact inputs become effective.
Soft Unloading From A Load Sharing Or A Base Loaded System The unload sequence is initiated by opening the “Load/Unload” contact. The DSLC-2 control then ramps the load down to zero at the preset rate. When the load reaches the unload trip level setpoint, the “Breaker Open” relay, terminal 47/48, is momentarily deactivated to initiate the opening of the generator breaker.
When the trip level is reached, the breaker open command relay is momen- tarily deactivated to separate the generator from the utility. When the “CB Aux” contacts open, the DSLC-2 con- trol goes into droop behavior and keeps the frequency on the initial state.
Controlled By MSLC-2 Utility Mode A DSLC-2 only listen to a MSLC-2 when in load sharing mode. This means that the “CB Aux” and the “Load / Unload” inputs are closed. The DSLC-2 will display “Baseload” for the Load control mode (parameter 4603).
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Reverse Power Relay Description ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Setting Reverse power trip (parameter 7507) in Menu 2 to “Enabled” selects relay “Load switch” (terminal 43) as the reverse power trip output. The load switch will not operate based on the load switch PU and load switch DO settings when the Reverse power trip (parameter 7507) is enabled.
The Reactive load droop setting, on Menu 4 (parameter 5604), is = 0, then the biasing output remains on the last biasing level. The voltage regulator must have a droop CT installed with a 1 to 3 % droop ad- justment. Woodward always recommends to have a droop CT installed and active on the voltage regula- tor.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Var control The var control is active in • Base load control • Process control • With an active MSLC-2 control Adjustments when in var control • PID var control VAR control proportional gain (parameter 5613)
Whether var control or power factor control is enabled, internally the var setpoint for the generator is restricted from +100 % to -10 % rated reactive power. When the DSLC-2 is operating in the base load mode, process mode or with an active MSLC-2 control, it will not allow the kvar output of the generator to increase above 100 % or below -10 % of the Generator rated reactive power (parameter 1758).
Var Sharing ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ When either var or power factor control is configured and the DSLC-2 control is operating in isochronous load sharing mode, var sharing is automatically selected. Var sharing adjusts the voltage regulators so that all genera- tors carry the same proportion of reactive load by balancing the kvar on all units. A Voltage reference setpoint, Menu 4 (parameter 5600) is provided to define the isolated operating voltage.
Introduction ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The process control function of the DSLC-2 will control any process where the controlled parameter is deter- mined by the generator load and the controlled parameter can be monitored as an analog input signal (process in- put). The control compares the input signal to the process reference or the external load reference signal if it is used and adjusts the generator load to maintain the desired setpoint.
Segment connectors inform the DSLC-2s and MSLC-2s which generators and utilities are connected. Through the segmenting the DSLC-2 / MSLC-2 can recognize all the time with which other units they are inter- connected. So the DSLC-2s in the same segment are load share together or doing an independent load control.
The segment numbers have to follow a line and shall not branch. The information which segments are connected coming by discrete inputs terminals 141 to 148. All DSLC-2 and MSLC-2 have the same discrete in- puts to control the segmenting. The 8 segment connection feedbacks are over-all the same and are logically ORed to each other.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Figure 8-5: Isolated / utility parallel operation with multiple generator, tie-breaker and generator group breaker Figure 8-5 shows an application with 2 utility feeder breaker, 2 load segments and 2 generator group breaker. The segment line begins at the left side with the load A segment (segment no.1) and ends with the load B segment...
A main rule in the segmenting is that segment numbers have to follow a line without branches. At next are shown some application examples which are not covered by the DSLC-2 / MSLC-2 system. The application in Figure 8-7 and Figure 8-8 shows how the segment number line can branch. Another indication is the need for a segment breaker between segment 3 and 5, which does not exists.
(parameter 3188) has to be configured for. Each unit gets its own slave ID usually related to the own Device number (parameter 1702). The remote control has to be configured for either RS-485 or Ethernet. Furthermore the DSLC-2 / MSLC-2 al- lows distribute functions to discrete inputs and to protocol bits.
Interface Connection Via Ethernet By Modbus/TCP Stack The DSLC-2 / MSLC-2 system provides the Ethernet channel B for Modbus/TCP connection. Each unit gets an own Modbus slave address. The DSLC-2 as the MSLC-2 allows to configure each parameter or to inform about each measure.
DSLC-2 - Digital Synchronizer and Load Control Chapter 10. Interface Interface Overview ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The device has several communication interfaces which are described below. Figure 10-1: DSLC-2 - interface overview (housing - side view) Number Labeled Protocol Network A Network B...
It is important to know that the load share and load-dependent start/stop functionality is subject to a multi-master principle. This means that there is no dedicated master and slave function. Each DSLC-2 decides for itself how it has to behave. The benefit is that there is no master control, which may cause a complete loss of this functionality in case it fails.
(PLCs). It has become a de facto standard communications protocol in industry and is now the most commonly available means of connecting industrial electronic devices. The DSLC-2 / MSLC-2 supports a Mod- bus RTU Slave module. This means that a Master node needs to poll the slave node. Modbus RTU can also be multi-dropped or in other words, multiple Slave devices can exist on one Modbus RTU network, assuming that the serial interface is a RS-485.
DSLC-2 - Digital Synchronizer and Load Control Address Range The DSLC-2 / MSLC-2 Modbus Slave module distinguishes between visualization data and configuration & re- mote control data. The different data is accessible over a split address range and can be read via the "Read Hold- ing Register"...
AC measurement data, switch states and various other information may be polled. According to the DSLC-2 / MSCL-2 Modbus addressing range, the visualization protocol can be reached on addresses starting at 450001. On this address range it is possible to do block reads from 1 up to 128 Modbus registers at a time.
DSLC-2 - Digital Synchronizer and Load Control Configuration The Modbus interface can be used to read/write parameters of the DSLC-2 / MSLC-2. According to the DSLC-2 / MSLC-2 Modbus addressing range for the configuration addresses, the range starts at 40001 and ends at 450000.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control DSLC-2 Interface Remote Control For a remote setting of the control setpoints, it is necessary to use the interface setpoints instead of the internal setpoints. No password is required to write this value. All other setpoint sources are configured accordingly. Con- trol orders can be sent via Ethernet (Modbus/TCP) or RS-485 Modbus RTU.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Figure 10-3: Modbus - sending binary digital orders over interface Parameter Setting range Default Description 7645 Release These single bits control if a function shall be switched by discrete discrete in- input or communication interface.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter Setting range Default Description 7644 Discrete in- These single bits switch the single functions if they are released puts over by parameter ID 7645. communica- tion interface Bit 01 = 1 Check...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Figure 10-4: Modbus – loss of connection Example 1: Active Power Interface Setpoint Baseload The setpoint for active power control is a long integer to provide a wide range from 1 to 999999.9 kW. Negative values are not allowed.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Example 2: Power Factor Interface Setpoint The setpoint for the power factor control is set as a value between -710 to -999, 1000, 999 to 710. A negative value is capacitive, a positive value is inductive, 1000 = cosphi 1. Other values are not accepted by the unit. This setpoint will be accepted, if the power factor setpoint is selected via ToolKit.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Changing Parameter Settings Via Modus ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Parameter Setting NOTE The example tables below are excerpts of the parameter list in Chapter: “Configuration & Operation“. NOTE Be sure to enter the password for code level 2 or higher for the corresponding interface to get access for changing parameter settings.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Example 2: Addressing the generator rated voltage: Par. ID. Parameter Setting range Data type 1766 Generator rated voltage 50 to 650000 V UNSIGNED 32 Table 10-10: Modbus – generator rated voltage Modbus address = 40000 + (Par.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Remotely Resetting The Default Values Modbus Via RS-232 / RS-485 Or Modbus TCP/IP It is possible to remotely reset the unit to its default values through Modbus (via RS-232 / RS-485) or Modbus TCP/IP using the parameter 10417 and 1701.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control In order to reset the default values, parameter 1701 must be enabled. Example: The default values are to be reset. Modbus address = 40000 + (Par. ID + 1) = 41702...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Modbus Parameters ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ NOTE The following parameters are available for configuring the Modbus modules on the serial interfaces. Refer to Chapter: “Configuration & Operation“ for detailed information about all parameters. Serial Interface 1...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Appendix A. Technical Data Nameplate Item number Item revision number Serial number (numerical) Serial number (barcode) Date of production (year-month) Type Description (short) Type Description (long) Details Technical data Approval Approvals Measuring values (voltages) –...
Page 202
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Discrete outputs – potential free Contact material AgCdO General purpose (GP) (V cont, relays 2.00 Aac@250 Vac 2.00 Adc@24 Vdc 0.36 Adc@125 Vdc 0.18 Adc@250 Vdc Pilot duty (PD) (V cont, relays B300 1.00 Adc@24 Vdc...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Environmental Data ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Vibration Frequency Range – Sine Sweep 5 Hz to 100 Hz • Acceleration Frequency Range – Random 10 Hz to 500 Hz • 0.015G² / Hz Power Intensity •...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Appendix B. Useful Information Connecting 24 V Relays ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Interferences in the interaction of all components may affect the function of electronic devices. One interference factor is disabling inductive loads, like coils of electromagnetic switching devices. When disabl- ing such a device, high switch-off induces voltages may occur, which might destroy adjacent electronic devices or result interference voltage pulses, which lead to functional faults, by capacitive coupling mechanisms.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Appendix C. Data Protocols Data Protocol 5200 ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Modbus Modicon Size Format Parameter Description DSLC-2 Multiplier Units Adress Adress (BUS-data * Multiplier = real value) 50000 450001 16 bits signed Protocol-ID, always 5200...
Page 207
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Modbus Modicon Size Format Parameter Description DSLC-2 Multiplier Units Adress Adress (BUS-data * Multiplier = real value) 50029 450030 16 bits signed Auxiliary busbar L1-N scaled defined by index 3182 (modicon Adress 450003)
Page 208
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Modbus Modicon Size Format Parameter Description DSLC-2 Multiplier Units Adress Adress (BUS-data * Multiplier = real value) 50058 450059 16 bits signed 4635 Reactive Load Control Mo- 0: Inactive 1: Off...
Page 209
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Modbus Modicon Size Format Parameter Description DSLC-2 Multiplier Units Adress Adress (BUS-data * Multiplier = real value) 0 (reserve) Mask: 8000h 0 (reserve) Mask: 4000h 3-Position Controller Mask: 2000h Volt./ReactPow raise...
Page 210
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Modbus Modicon Size Format Parameter Description DSLC-2 Multiplier Units Adress Adress (BUS-data * Multiplier = real value) 0 (reserve) Mask: 8000h 0 (reserve) Mask: 4000h 0 (reserve) Mask: 2000h 0 (reserve)
Page 211
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Modbus Modicon Size Format Parameter Description DSLC-2 Multiplier Units Adress Adress (BUS-data * Multiplier = real value) Load/Unload Switch (DI8) Mask: 0080h (Energized=Load) Base Load Control Switch Mask: 0040h (DI7) Voltage Lower Switch (DI6)
Page 212
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Modbus Modicon Size Format Parameter Description DSLC-2 Multiplier Units Adress Adress (BUS-data * Multiplier = real value) 50102 450103 32 bits signed Total generator reactive power 50104 450105 32 bits signed...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Appendix D. Parameter Overview Introduction ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Parameter List Columns The parameter list consists of the following columns, which provide important information for each parameter: Namespace X The namespaces 1 and 2 are used to combine all parameters within functional groups.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Parameter List ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Namespace1 Namespace2 Parameter Text Setting Range Default Value Data Type MENU 0 7584 Synchronizer timeout alarm Off ; 0 UNSIGNED Alarm1 ; 1 Alarm2 ; 2 Alarm3 ; 3...
Page 215
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Namespace1 Namespace2 Parameter Text Setting Range Default Value Data Type MENU 1 4541 Voltage window 00.50 to 10.00 % 00.50 % INTEGER 16 MENU 1 4700 Voltage synchronizer pro- 000.01 to 100.00 001.00...
Page 216
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Namespace1 Namespace2 Parameter Text Setting Range Default Value Data Type MENU 2 4549 Load ramp rate 000.01 to 100.00 %/s 003.00 %/s INTEGER 16 MENU 2 5510 Frequency trim 000.01 to 100.00 000.50...
Page 217
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Namespace1 Namespace2 Parameter Text Setting Range Default Value Data Type MENU 4 5608 Voltage control initial state 000.0 to 100.0 % 050.0 % UNSIGNED MENU 4 5610 Voltage trim proportional 000.01 to 100.00 000.50...
Page 218
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Namespace1 Namespace2 Parameter Text Setting Range Default Value Data Type MENU 5 Transformer 1803 Bus PT secondary rated 050 to 480 V 120 V UNSIGNED volt. MENU 5 Transformer 1804 Bus PT primary rated vol-...
Page 219
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Namespace1 Namespace2 Parameter Text Setting Range Default Value Data Type MENU 5 5802 Upper frequency limit 100.0 to 150.0 % 110.0 % UNSIGNED MENU 5 5803 Lower frequency limit 050.0 to 100.0 % 090.0 %...
Page 220
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Namespace1 Namespace2 Parameter Text Setting Range Default Value Data Type MENU 6 Voltage Bias 5215 Selected hardware type Off ; 0 UNSIGNED User defined ; 1 0-10mA / 0-5V ; 2 0-20mA / 0-10V ;...
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ If a control (or any part of an electronic control) is to be returned to Woodward for repair, please contact Wood- ward in advance to obtain a Return Authorization Number. When shipping the unit(s), attach a tag with the fol- lowing information: •...
Stuttgart [+49 (0) 711 789 54-0]. They will help expedite the processing of your order through our distributors or local service facility. To expedite the repair process, contact Woodward in advance to obtain a Return Authoriza- tion Number and arrange for issue of a purchase order for the unit(s) to be repaired. No work can be started until a purchase order is received.
+49 (0) 711 789 54-100 e-mail: stgt-info@woodward.com For assistance outside Germany, call one of the following international Woodward facilities to obtain the address and phone number of the facility nearest your location where you will be able to get information and service. Facility...
Colorado or from one of many worldwide Woodward offices or authorized distributors. Field engineers are expe- rienced on both Woodward products as well as on much of the non-Woodward equipment with which our prod- ucts interface. For field service engineering assistance, please contact us via our toll-free or local phone numbers, e-mail us or use our website and reference field service.
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control Technical Assistance ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ If you need to telephone for technical assistance, you will need to provide the following information. Please write it down here before phoning: Contact Your company ____________________________________________________ Your name _______________________________________________________...
Page 226
Phone +49 (0) 711 789 54-0 • Fax +49 (0) 711 789 54-100 stgt-info@woodward.com Homepage http://www.woodward.com Woodward has company-owned plants, subsidiaries and branches, as well as authorized distributors and other authorized service and sales facilities throughout the world. Complete address/phone/fax/e-mail information for all locations is available on our website (www.woodward.com).
Need help?
Do you have a question about the DSLC-2 and is the answer not in the manual?
Questions and answers