If the password is not entered correctly the panel will display
Once the current password has been entered, the panel will prompt for the configuration parameter being changed.
If the password has been lost:
Power down the DVP-120C.
Remove the Jumper Shorting Connector from the EXT header and place the Jumper Shorting Connector onto
the top two pins of the SYS header.
Power up the DVP-120C. The first display is the current password on the unit.
Remove the Jumper Shorting Connector from the SYS header and install back onto the two bottom pins of
the EXT header.
Use only for monitoring the gases which the sensors and equipment are designed to
detect. Failure to do so may result in exposures to gases not detectable and result in
serious injury or death. For proper use, see supervisor or User manual, or Contact
Technical Support at 1-844-325-3050.

4.13.3 Configure Sensors Submenu

There is a list of parameters for each sensor in the system, either currently wired or configured but presently
disconnected. The left and right cursor keys can be used to move from one sensor to another and the up and down
keys will scroll through the parameters for the particular sensor.
4.13.3.1 Sensor Summary
This display example shows that the sensor on channel 01 has been configured as a Carbon Monoxide sensor with
an Alarm level of 200ppm and a Warning level of 50ppm.
Notice that the sensor number, 01 in this example, is underlined. This indicates that the digit keys can be used to
jump to a particular channel, even if there is no sensor connected to the channel.
4.13.3.2 Sensor Type
REV – 1.0
Figure 4-51 Password Prompt
W r o n g
P a s s w o r d
Figure 4-52 Wrong Password Prompt
WARNING
S e n s o r
0 1
A :
2 0 0
W :
Figure 4-53 Sensor Summary
S e n s o r
0 1
T y p e : 1
[34-8708-4770-8 ]
C O
5 0
C O
40 |