5 BACnet

5.1 General Information

Following standard objects defined by BACnet are used in DVP-120C:
a. Analog Input
b. Binary Input
BACnet objects available for each detector connected to DVP-120C are as follows:
5.1.1 Analog input – Sensor ID
The value in the BACnet object refers to the Sensor ID/Type of Macurco Gas detector. Values of 1 to 8 are only valid
values.
5.1.2 Analog Input – Gas Reading
This represents the gas reading of the detector. If the reading is not reliable then it will have value 6553.5. The
reading may be unreliable for any of the following reasons:
Registration Status of MRS-485 is non-zero (it is non-zero during detector warm-up period, trouble code,
MRS-485 registration in progress, and other miscellaneous MRS-485 error indicated by red Status LED in
MRS-485).
A successful request/response has not been detected for the reading (i.e. a timeout occurred, or a
detector does not exist).
The reading is under or over range DVP-120C compares the current reading of a detector with its range
and anytime it is outside the range, it will set the gas reading to 6553.5.
Invalid Sensor ID Type (1 - 9 are the only valid values).
5.1.3 Binary Input – MRS Trouble
This binary input object is set (i.e. the value is 1) when there is an error in MRS-485.
5.1.4 Binary Input – Over Range
This binary input object is set when reading from the detector is over the range.
5.1.5 Binary Input – Trouble
This binary input object is set when the detector is in trouble condition.
5.1.6 Binary Input – DVP Com Error
If the panel stops making Modbus request to the detectors for a specified timeout period of 3 seconds, then a
timeout event is triggered, and all gas reading is set to 6553.5, and DVP Com Error Binary Input data is set to 1. If
timeout event is not triggered value is set to 0.
One way to find out Modbus Address and information type is to look at the value of the property "Object Name".
E.g. "S13 Sensor ID" meant address is 13 and information contained by BACnet object is "Sensor ID".

5.2 Macurco Network Parameter Utility (NPU)

Macurco Network Parameter Utility is used to configure BACnet network settings in DVP-120C via USB connection.
In addition to this, it allows updating the panel with BACnet configuration in the field and automatically manages
device firmware dedicated for BACnet functionality. To receive the latest version of Macurco NPU, as well as
firmware and configurations, download the Macurco NPU from our website
REV – 1.0
[34-8708-4770-8 ]
http://www.macurco.com/downloads/
.
52 |