When all indicators have been silenced, the display will show that alarms have been silenced for five minutes. After
any key is pressed (or five seconds), the display will return to normal mode.
If Relay 1 is configured as an ALARM relay, it will be turned on when an alarm condition is recognized.

4.6 Warning Status Display

When any sensor indicates a gas level that is at or above the configured warning level for the sensor, the panel will
enter WARNING mode during which the internal buzzer will sound, the alarm/warning lamp will be amber, and the
LCD will show the sensor type and channel number.
The display will cycle through all sensors that are signaling warning levels, at five seconds per display. Pressing any
key (except HUSH) will advance the display to the next sensor that is signaling a warning level.
If the buzzer and/or an external horn and/or external strobe are connected and configured to signal a warning
condition, they will also sound when a warning condition occurs. There is a configurable delay before the horn or
strobe will sound, see sections
Configure Relays, Horn &
Strobe.
When the HUSH key is pressed, the internal buzzer will be silenced for fifteen (15) minutes. If the horn or strobe turn
on delays have not finished, then they will also be silenced. If the delays have finished, the HUSH key must be held
for three (3) seconds in order to silence the horn and strobe.
When all indicators have been silenced, the display will show that warnings have been silenced for fifteen minutes.
After any key is pressed (or five seconds) the display will return to normal mode.

4.7 Trouble Status Display

If a sensor fails, a connection is lost or the panel itself detects a failure of its own, the panel will enter TROUBLE
mode during which the internal buzzer will sound, the power lamp will be yellow, and the LCD will display the
specific sensor identified.
Possible trouble conditions are:
Any configured channel has less than 4 mA flowing in the current loop
A sensor is reporting a trouble condition
REV – 1.0
A L A R M S I L E N C E D
F O R
5
M I N U T E S
Figure 4-7 Alarm Silenced message
W A R N I N G
C O
S E N S O R
Figure 4-8 Warning display
4.13.5 Configure Horn
Submenu,
W A R N I N G
F O R
1 5
M I N U T E S
Figure 4-9 Warning Silenced message
[34-8708-4770-8 ]
0 2
4.13.6 Configure Strobe
S I L E N C E D
Submenu, and
4.13.4
26 |
P a g e

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mrs-485Dvp-485b

Table of Contents