9.4 Configure Zones Submenu

9.4.1 See section
4.13.7 Configure Zones Submenu
Definitions:
Zone – Defines Sensor Input & Relay / Alarm Output
Group – Set of Sensors of the same type and output within the same zone
Average – Activation based upon an average of sensors in a group
Voting – Number of sensors needed to be above trip point to activate the output
Quorum – Number of sensors need to vote, 1 = any sensor
Press Menu to display Hardware Summary
↑ x 4 Configure Zones
→ Zone 1 Controls
R_ R_ R_ H_ S_
Enter (underlined) number of output for zone
R = Relay (1, 2 and 3), H = Horn (4), S = Strobe (5)
↑ Configure Group 1
Sensor type - enter #
1=CO, 2=NO2, 3=Combustible, 0=None
↑ Sensor Number - enter a two-digit number for each sensor to be included in the group (e.g., 01, 02, 03...12.) from
01 through 12.
↑ Rising (activation) Trip point
REV – 1.0
( m m : s s )
Figure B-19 Minimum on Time
for more detail
Z o n e
1
C o n t r o l s
R 1
R 2
R 3
Figure B-20 Zone Controls
Z 1
G r o u p
S e n s o r
T y p e : 2
Figure B-21 Zone Controls
Z 1
G r o u p
S e n s o r s : 0 2 , 0 4 , 1 1
Figure B-22 Sensor Selection
Z 1
G r o u p
R i s i n g :
[34-8708-4770-8 ]
0 1 : 0 0
H 4
S 5
1
N O 2
1
N O 2
1
N O 2
2 . 5 p p m