Open your BACnet Software Solution and verify the Macurco DVP-120C BACnet Panel is communicating
with the software.
5.3.2 BACnet MS/TP to BACnet/IP
Using a standard serial to Ethernet media converter will not work with BACnet MS/TP due to the strict timing
requirements of the protocol. A BACnet Router must be used to perform the conversion from BACnet MS/TP to
BACnet/IP.
5.4 BACnet Software
There are a number of software applications available to read the BACnet output of the Macurco DVP-120C Control
panel. For more information on these please contact Macurco Support at 1-844-325-3050 or
6 Troubleshooting
The DVP-120/DVP-120C is tested at the factory for reliable operation. Most problems can be traced to the set-up of
configurable features and modes, system wiring or trouble with the sensors.
Failure to follow instructions outlined in this user manual can result in sickness or death.
6.1 System Status Light
The system status light (section
whenever the controlling firmware detects a Trouble condition. Possible trouble conditions are:
REV – 1.0
Figure 5-3 RS-485 to Ethernet (TCP/IP)
WARNING
4
Operation) is normally green indicating power is present but will change to yellow
[34-8708-4770-8 ]