Features; Specifications - Macurco DVP-120C User Instructions

Detection and ventilation control panel with bacnet
Table of Contents

Advertisement

Macurco DVP-120C Manual

2.4 Features

LCD display showing the status of each transducer and relay
External keypad for user selection of the transducer/alarm display and setting the configuration (password
protected)
Up to three ventilation control zones can be defined
Each zone can be controlled based on transducer signals and/or time of day
Each relay is configurable with a delay before activation and minimum on time
Fail-safe operation can be implemented
Lockable NEMA 1 type enclosure
Modular input and output connectors
One RS-485 digital input channels - 99 addressable sensors
RS-485 digital output channel for BACnet
Compatible with Macurco CM-6, TX-6-ND, and MRS-485 adapter, Horn & Strobe Combo
Three 10A, 240 VAC SPDT Dry Contact relays
24VDC Drivers for external Horn and Strobe
BTL Listed
ETL Listed to UL 2017
Where required by federal, state, local regulations or the Authority Having Jurisdiction, DVP-120C is required to be used with Listed
1
Horn/Strobe model 78-2900-0211-X* to meet the 85dB(A) Audibility requirements of Standards UL 2017.
*Where "X" represents lens cover color, R for red lens cover, G for green lens cover, B for blue lens cover, O for amber lens cover, C for
clear lens cover.

2.5 Specifications

Size:
10.5" x 12.5" x 2." (267 mm x 318 mm x 51 mm)
Weight:
6 ½ lb (2.9 kg)
Enclosure:
NEMA 1 Type
Operating Temperature:
Operating Humidity:
Power Input:
90 – 250 VAC, 1 Amp, 47 – 63 Hz, single phase
Relay Rating (3):
LCD Display:
2 rows of 16 characters with backlight
Status Indicators (LED): Power/Trouble, ALARM/warning, Hush, Relay 1, Relay 2 & Relay 3
Audible indicator:
External Drivers (2):
Carbon Monoxide (CO) Range: 0 – 200ppm
Nitrogen Dioxide (NO2) Range: 0 – 20ppm
Relay on Delay: 0 – 15 minutes in 1 second increments
Relay Minimum Run Time:
REV – 1.0
1
(Type SM)
32° to 120°F (0° to 49°C)
0% to 90% RH non-condensing
SPDT, 120/240 VAC, 10 A resistive
Internal buzzer, 90 dBA at 1ft
24VDC, maximum 250 mA
0 – 15 minutes in 1 second increments
[34-8708-4770-8 ]
9 |