Calibration Overdue Trouble Display - Macurco DVP-120C User Instructions

Detection and ventilation control panel with bacnet
Table of Contents

Advertisement

Macurco DVP-120C Manual
DVP-120C displays the address of the detector with calibration due warning. If there are more than one detector
with calibration due warning, then display scrolls every 5 seconds to display all detectors with calibration due
warning.
During Calibration Due Warning, the warning LED will be ON. Buzzer, Horn and Strobe of the panel will be activated
based on Warning Signal Configuration in CONFIGURE SIGNAL.
When the HUSH key is pressed, the internal buzzer will be silenced. If the horn or strobe turn on delays have not
finished, then they will also be silenced. If the delays have finished, the HUSH key must be held for three (3) seconds
in order to silence the horn and strobe. Silence period is dependent on time left to calibration. Following table
shows silence period for different time to calibration.
When all indicators have been silenced, the display will show that calibration due warning indication have been
silenced for corresponding silence period. After approximately 5 seconds the display will return to normal mode.
Only a calibration due warning with lower silence interval (refer Table 4-2) will reset the HUSH and panel will go back
to state indicating Calibration Due Warning.
When in normal mode, for detectors with Calibration Due Warning silenced panel will display current gas reading
alternating with "Cal. Due" every second.

4.11 Calibration Overdue Trouble Display

When the panel detects a detector with Calibration Overdue condition it will go into trouble state. This trouble has
higher priority than a regular trouble condition. This feature is applicable only for detector with calibration period
feature.DVP-120C displays the address of the detector with calibration Overdue trouble. If there are more than one
detector with calibration overdue condition, then display scrolls every 5 seconds to display all detectors with this
trouble condition.
During Calibration Overdue trouble, the trouble LED will be ON. Buzzer, Horn and Strobe of the panel will be
activated based on Trouble Signal Configuration in CONFIGURE SIGNAL.
REV – 1.0
C a l i b r a t i o n
C O
S e n s o r
Figure 4-16 Calibration Due
Time till Calibration
>14 days, and <30 days
>7 days, and <14 days
< 7 days
Table 4-2 Calibration Due Silence Period
C a l. D u e
S I L E N C E D
F O R
7 d a y s
Figure 4-17 Calibration Due Silenced
C a l i b r a t i o n
C O
S e n s o r
Figure 4-18 Calibration Required
[34-8708-4770-8 ]
D u e
0 2
Silence Period
14 days
7 days
1 day
R e q.
0 2
29 |
P a g e