System Configuration - Macurco DVP-120C User Instructions

Detection and ventilation control panel with bacnet
Table of Contents

Advertisement

Macurco DVP-120C Manual
The display will cycle through all zones that are controlling the horn or strobe and are signaling, at five seconds per
display. Pressing any key (except HUSH) will advance the display to the next zone that is signaling.
When the HUSH key is held for three (3) seconds, the horn and/or strobe will be silenced for fifteen (15) minutes.
When silenced, the display will show that zone signals have been silenced for fifteen minutes. After any key is
pressed (or five seconds) the display will return to normal mode.

4.13 System Configuration

The configuration menus can be entered from normal mode by pressing the MENU key. While in configuration
mode, the user can review all configuration parameters to check the current operating conditions. As an aid when
configuring the control panel, the first entry in the top menu summarizes the number of sensors and relays that the
panel is currently recognizing. Be sure that the 4-20mA output on each sensor is set to "On".
The MENU key is also used to return to a higher-level menu and finally exit the configuration menus back to normal
mode. When exiting from the menu system to normal mode, if any configuration changes have been made, the
panel will ask whether changes are to be saved.
Pressing the zero (0) key at this point will cancel all changes except time and day of week. Pressing the one (1) will
save all changes to memory, and the changes will then become effective in controlling the ventilation system.
While the DVP-120 is in the configuration mode, alarm and ventilation control functions continue in the background
with the previously set configuration values. If an alarm condition is detected, the alarm lamp, the buzzer, the horn
and the strobe will operate as configured but the LCD will not display the detailed information. The HUSH key can be
used to silence any alarm, warning or trouble indicators without having to exit the configuration mode. If the MENU
key is used to exit the configuration mode before using the HUSH key, the LCD will display the cause of the audible
indicator.
The numeric keys are used to change the parameter displayed. The underlined character, or space, on each display,
indicates what will be changed by the digit keys.
The left and right cursor keys will enter the submenu and scroll through the items of the same type where
appropriate, e.g. enter the Configure Sensors submenu and scroll through the parameter lists for the existing
sensors.
REV – 1.0
Figure 4-20 Zone Signal Display
Z O N E
S I L E N C E D
F O R
1 5
M I N U T E S
Figure 4-21 Zone Signal Silenced
5
S E N S O R S
3
R E L A Y S
Figure 4-22 Hardware Summary
S a v e
C o n f i g . ?
( 0 = N O , 1 = Y E S )
Figure 4-23 Save Configuration? Prompt
[34-8708-4770-8 ]
F O U N D
F O U N D
31 |
P a g e

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mrs-485Dvp-485b

Table of Contents