SRAM
"OK"?
No
No
The user data backed up in the SRAM of the SIMOTION P320‑4 is used.
1)
The user data backed up in the SRAM image on the storage medium of the SIMOTION P320‑4 is
2)
used.
The user data backed up in the SRAM backup on the storage medium of the SIMOTION P320‑4 is
3)
used.
11.5.3

After new installation / update of the SIMOTION P Kernel

If a compatible SIMOTION P Kernel is installed on an already commissioned
SIMOTION P320‑4, the user data backed up in the SRAM is retained.
However, the current software version of the SIMOTION PP320-4 must be identical to the
software version with which the backed-up user data of the SRAM was created.
Now SIMOTION P320-4 is immediately ready to run again.
Note
If you do not want the backed up user data to be used again, you will have to recommission
the SIMOTION P320-4.
Note
Restart of SIMOTION P320-4 required
After a new installation or update of the SIMOTION P Kernel, a restart of the SIMOTION P320-4
is generally required.
If the device is not restarted, the new SIMOTION P Kernel is not activated and you continue
to work with the old firmware.
11.5.4

After restoring a backup copy

If a backup copy (storage medium image) of a commissioned SIMOTION P320-4 is reloaded,
the backed-up user data stored in the SRAM of the SIMOTION P320‑4 is used.
Now SIMOTION P320-4 is immediately ready to run again.
SIMOTION P320-4 E / P320-4 S
Commissioning and Hardware Installation Manual, 11/2016
SRAM image
SRAM backup
(storage medium)
(storage medium)
"OK"?
"OK"?
No
Yes
No
No
Service and maintenance
11.5 Special power-up situations
User data
Note
used
BACKUP
No message box or
3)
alarms
Overall reset
Required
191