5.6 Installing the SIMOTION P320-4 in the control cabinet
Note
To ensure secure vertical mounting on standard rails, a standard rail ground terminal should
be mounted beneath the device.
Mounting/installing the device
Examples of mounting types
Material
Concrete
Plasterboard
(min. 13 mm thick)
Metal
(min. 2 mm thick)
NOTICE
Observe the total weight of the SIMOTION P320-4
Ensure that the wall can hold four times the total weight of the device (including mounting rail
and additional expansion modules).
Removing the device from the mounting rails
● Push the device down until the bottom clamp releases the device.
● Swing the device away from the rails.
Additional references
Further information on standard rail and vertical mounting can be found in the
SIMOTION P320-4 E / P320-4 S Manual.
90
Bore diameter
8 mm diameter
60 mm depth
14 mm diameter
5 mm diameter
Fixing
Wall plug: 8 mm diameter
50 mm length
Screws: 4 mm diameter
50 mm length
Cavity fixings: 4 mm diameter
50 mm length
Metal screws M 4: 4 mm diameter
15 mm length
SIMOTION P320-4 E / P320-4 S