5.3.3 Sealing end on a building's structure

If HVI Conductors are installed on a building's structure, the calculated separation distance "s" in the
sealing end range from the metal parts in the building's structure must be maintained.
The sealing end range ranges from the EB connection element to the connection of the earth connec-
tion element (see Fig. 19)
The mechanical contact of the EB spring element (semiconductive special sheath) allows to discharge
lightning impulse voltages to a reference potential. To this end, a conductive connection to the next
equipotential bonding system (equipotential bonding level) of the installation is required.
A UNI disconnecting clamp (Part No. 459 129) can be used to connect the earth connection element of
the HVI Conductor to the earth-termination system.
Detail A:
EB connection element
Detail B:
connection of the earth connection
element
Figure 19 Sealing end range on a building's structure
32
.
EB connection element
Detail A
(Part.-No. 410 229)
connection to the
equipotential bon-
ding system of the
HVI Conductor
building's structure
earth connection
element
Detail B
UNI disconnecting clamp,
e.g. Part No. 459 129
s
down conductor
EB
building
holder, e.g. Part No.
Part.-No. 275 229
s
connection to the
earth-termination
system