9. Checklist for installing HVI Conductors

If all the questions in the checklist below are answered with "yes", it can be assumed that the
HVI long Conductor is installed correctly. The checklist can be downloaded at
http://www.dehn-international.com/en.
Checklist for HVI Installation
Address of the test object:
Name:
Contact partner:
Street:
Postcode, Place:
Phone:
Item Question
1
Is the whole system positioned in the protected area?
2
Has the separation distance been calculated?
(down conductor to the earth-termination system, isolated system with connection to existing
external lightning protection system or lightning equipotential bonding on roof level)
3
Is the maximum equivalent separation distance specified by DEHN for the application of the
HVI Conductor kept?
HVI light Conductor / DEHNcon H
HVI Conductor
HVI power Conductor
4
Is the calculated separation distance kept in the range of the sealing end?
5
Is the supporting tube and, if required, the equipotential bonding element of the sealing end
correct, i.e. only connected with the equipotential bonding / the lightning equipotential bond-
ing of the system?
6
Is the minimum distance of 0.2 m kept between HVI Conductors routed in parallel and has the
connection to opposite down conductors been considered?
7
Has the minimum bending radius been kept?
HVI light Conductor (dark grey outer coating)
HVI Conductor (black outer coating)
HVI Conductor (grey outer coating)
HVI power Conductor (black outer coating)
8
Is the equipotential bonding element of the sealing end in contact with the semiconductive
layer (not grey coating)?
9
Has the supplementary information in DEHN installation instructions No. 1501/No.1892
been considered for installation of the HVI / HVI power Conductor in hazardous areas?
10 Did you exclusively use (tested) components of the manufacturer DEHN?
Place
Figure 24 Checklist
s ≤ 0.45 m in air
s ≤ 0.75 m in air
s ≤ 0.9 m in air
Date
Signature of tester
s ≤ 0.9 m solid material
s ≤ 1.5 m solid material
s ≤ 1.8 m solid material
200 mm
200 mm
230 mm
270 mm
Company
Rating
YES
NO