2.2
Technical data
Outer sheath
Equivalent separation
distance of the
HVI Conductor
Lightning current carrying capability
Outer diameter
Minimum bending radius
Permanent temperature range
(in case of fixed installation)
Ambient and conductor temperature
during installation and processing
Maximum tensile load
Solid/stranded inner conductor (copper)
Table 1
Technical data of HVI Conductors
2.3
Chemical properties
Reaction to fire (self-extinguishing)
Weather-proof (UV-stabilised)
Fire load
Table 2
Chemical properties of HVI Conductors
Air
Solid material
Black, RAL 9011
≤ 75 cm
≤ 150 m
150 kA (H1)
20 mm
200 mm
-30° to +70°C
-5° to +40°C
19 mm²
Black, RAL 9011
No
Yes
3,6 kWh/m
Grey, RAL 7035
23 mm
230 mm
950 N
Grey, RAL 7035
Yes
4,3 kWh/m
7