baltur TBML 80 MC User Instructions page 63

Dual fuel gas/light oil two-stage progressive/modulating burners
Table of Contents

Advertisement

Available languages

Available languages

ELECTRODE / IONISATION PROBE ADJUSTMENT DIAGRAM
1- Diffuser
2- Internal diffuser
3- Flame disk
4 - Ignition electrodes
5- Nozzles
6- Nozzle holder
FUEL/AIR REGULATION SERVOMOTOR
SERVOMOTOR SQN72.6E5A20BT CAM REGULATION
1 Camshaft-motor coupling insertion
and exclusion pin.
2 Reference scale
3- Position indicator
I
Maximum air opening regulation cam (130°)
II Total air closure (burner stopped)( 0°)
III Air opening regulation cam for minimum gas (30°)
IV 1st diesel flame air regulation cam (50°)
V Diesel 2nd flame valve activation cam (grater than cam IV) (80°)
Use the corresponding rings to modify the adjustment of the utilized cams
(I - II - III....). The ring pointer indicates the rotation angle set for each cam on
the respective reference scale.
After installing the nozzles, check the correct position of the electrodes and disk
according to the following measurements indicated in mm.
It's advisable to check levels after every intervention on head.
RECOMMENDED NOZZLES:
STEINEN type SS 45° (TBML 80 MC - 120 MC - 200MC)
MONARCH type HV 45° (TBML 160 MC)
A
TBML 80 MC
1 ÷ 1,5
TBML 120 MC
1 ÷ 1,5
TBML 160 MC
1 ÷ 1,5
TBML 200 MC
1 ÷ 1,5
2
25 / 36
0006081544_201408
B
C
20 ÷ 21
6 ÷ 7
20 ÷ 21
6 ÷ 7
20 ÷ 21
6 ÷ 7
20 ÷ 21
7 ÷ 8
CAM REGULATION
1
3
D
E
3 ÷ 4
5 ÷ 6
3 ÷ 4
8 ÷ 9
3 ÷ 4
8 ÷ 9
3 ÷ 4
8 ÷ 9