Removing And Replacing The Front Doors - Eaton 9355 User Manual

Hide thumbs Also See for 9355:
Table of Contents

Advertisement

UPS System Installation
4 4 . . 7 7
I I n n t t e e r r n n a a l l B B a a t t t t e e r r y y T T r r a a y y W W i i r r i i n n g g C C o o n n n n e e c c t t i i o o n n s s
NOTE
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE
PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
The UPS is intended to be operated only with batteries installed. When batteries are not installed a stabilizing
bracket is required to prevent a tip hazard.
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation. Initial
startup must be performed by an authorized Eaton Customer Service Engineer. Risk of electrical shock.
Servicing should be performed by qualified service personnel knowledgeable of batteries and required
precautions. Keep unauthorized personnel away from batteries.
Batteries can present a risk of electrical shock or burn from high short circuit current. The following
precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with
insulated handles; 3) Do not lay tools or metal parts on top of batteries; 4) Disconnect charging source prior
to connecting or disconnecting battery terminals; 5) Wear voltage rated gloves and electrical hazard
footwear.
When replacing batteries, replace with the same type and number of batteries or battery packs. Contact
your service representative to order new batteries.
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes and
may be extremely toxic.
Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will
be reduced if such grounds are removed during installation and maintenance.
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter
wiring can cause injury.
To access and install the internal battery trays and wiring connections (for both the 9355 UPS and EBCs):
1.
Verify that the input, output, and battery circuit breakers are in the OFF position
2.
If not already removed, remove the front door of each cabinet.
See paragraph
3.
If not already removed, remove the battery panel dead front.
50
Eaton 9355 UPS (20/30 kVA) User's Guide 164201626—Rev H0
To reduce electrical safety risks during transportation, the UPS is shipped with the
internal battery tray assemblies disconnected.

4.2 Removing and Replacing the Front Doors

DANGER
WARNING
WARNING
CAUTION
details on this process.