Matching The Utility Voltage - Compaq R12000 XR User Manual

Uninterruptible power system
Table of Contents

Advertisement

LCD Configuration and Status

Matching the Utility Voltage

Use configuration parameters to select the UPS voltage range (see Table 3-1).
If the utility voltage is within this range, the UPS supplies utility power to the output
receptacles.
If the utility voltage is outside this range, the UPS supplies battery power to the output
receptacles.
If the utility voltage frequently varies outside the operating range, update the UPS
configuration to match.
NOTE:
this chapter), you are setting the UPS output voltage.
Table 3-1: Voltage Ranges (VAC)
Nominal Utility
Voltage Level
200
208
220
230 (default)
240
To update the configuration:
1. Have a licensed electrician measure your utility voltage.
2. Use Table 3-1 to identify the operating range that most closely matches your nominal
utility voltage level.
3. Update the UPS output voltage as required. See the section, "Set Voltage," in this chapter
for more information.
3-2
When you set the voltage through the LCD panel (as described in the "Set Voltage" section of
Normal Utility
Voltage Range
166-240
166-248
176-264
184-276
192-288
UPS Output
Voltage
200
208
220
230
240
Compaq Uninterruptible Power System R12000 XR User Guide