Troubleshooting
Table 5-1: Main Module and Electronics Modules M1-M4 Active Alarms
LCD Display
X Alarms
Level 3 Overload –
Phase A
X Alarms
Level 4 Overload –
Phase A
X Alarms
Loss of
Redundancy
X Alarms
Loss of Sync-Bus
X Alarms
Low Battery
Shutdown
5-6
Cause of alarm
The UPS detects that the current load
has exceeded 110% of the maximum
capacity available, operating in
Non-redundant mode.
The UPS will transfer to Bypass mode
after 30 seconds of this sustained load
level.
The UPS detects that the current load
has exceeded 120% of the maximum
capacity available, which means it is
operating in Non-redundant mode.
The UPS will transfer to Bypass mode
within one second and remain in that
mode due to the excessive overload
condition.
The UPS detects that the current load
level has exceeded the maximum safe
load level limits that would provide
redundancy protection to the
electronics modules.
The system will continue to operate,
but will no longer be in Redundant
mode. The load could be at risk if an
electronics module fails.
The UPS detects that its electronics
modules are having trouble
synchronizing with the input utility
source. The most likely cause is a poor
utility source supplying the UPS.
While on battery, the UPS detects that
the battery voltage level has dropped
below the lowest preset threshold
value. The UPS will be shut down.
This normal alarm condition occurs at
the end of a battery discharge cycle.
The threshold represents the lowest
allowable battery discharge level for the
batteries before they can no longer
safely support the load. Once valid
utility returns, the UPS will assume the
load after a minimum charge level has
been restored to the batteries, and it
will begin a complete battery recharge
cycle.
Action to take
Reduce the load level to clear the
alarm. If the alarm persists after load
reduction, see the LCD panel to
determine which electronics module is
reporting overload.
Contact Technical Support for
assistance.
Reduce the load level to clear the
alarm. If the alarm persists after load
reduction, see the LCD panel to
determine which electronics module is
reporting overload.
Contact Technical Support for
assistance.
If redundant operation is desired,
reduce the load until the alarm clears.
Switch to Maintenance Bypass mode,
and restart the system.
Contact Technical Support for
assistance.
This is a normal operation.
Compaq Uninterruptible Power System R12000 XR User Guide
continued
continued