8 Operating
8.4.2 Menu 2: "Block & reset alarms"
Overview:
Block device
Release device
Main menu
Manual reset
Reset deep discharge
Test & status menu
Block & reset alarms
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 2
Block device
Release device
Manual reset
Block device
Reset deep discharge
Release device
Reset ISO-failure
Manual reset
ISO-failuresearch
Reset deep discharge
 Selection of
menu options
with the 
keys
 <ok>:
Block device
confirm selec-
Release device
Manual reset
tion
Reset deep discharge
 <Menu>: cancel
and return to
the previous
menu (any
changes en-
tered are saved)
 <ESC>: cancel
and return to
Block device
the previous
Release device
Manual reset
menu (any
Reset deep discharge
changes en-
tered are not
saved)
 flashing input
prompt
Release device
Manual reset
Reset deep discharge
Reset ISO-failure
Manual reset
Reset deep discharge
Reset ISO-failure
ISO-failuresearch
80
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
<ok>
This device
Menu 2.1:
all devices
Device address
Device name
Selection with the buttons
ween the displayed options.
Selection of a ZB-S system with
Device address referes to search
results in the substation setup
menu 3 «Basic settings»
<ok>
This device
Menu 2.2:
all devices
Device address
Device name
(Menu 2.3: only directly at the station)
<ok> initiates the function if this ope-
ration has been activated in the menu
option «Basic settings»:
Following a mains power failure, normal
operation will not be resumed automati-
cally when mains power is restored if
the "Manual reset (On)" option has been
(Menu 2.4: only directly at the station)
 <ok> initiates the function:
Following a "Deep discharge protection"
message in the main screen, the mes-
sage is acknowledged with this menu
option.
(Menu 2.5: only directly at the station)
<ok>
Find ISO failure
<ok>
this device
Menü 2.6:
all devices
cancel search
Selecection of cursor position with
<ok> starts the ISO failure search
<Menu>Cancel and back to menu 2
During the search all stations be
switched to blocked conditions!
Divergent to SKU CG-S 2x3 A, with the SKU CG-S 4x1.5 A and
SOU CG-S 2x4A only one isolation fault is registered for all
circuits of the module. Limitation of the isolation fault must
be implemented at the module by enabling the single circuits.
<ok> initiates the function:
All functions are cancelled;
all outputs will be isolated!
01
In case of mains failure occures no
battery operation.
bet-
These must be additionally separa-
ted on all poles before maintenance
work in end circuits. (see 10.3 Enab-
ling of end circuits with maintenance
work)
<ok> initiates the function:
The selected stations will be swich-
ted free and restart operation.
01
activated (menu «Basic settings/
Manual reset»).
This guarantees that the emer-
gency lighting remains on until it is
ensured that the general lighting
has been switched on again, e.g. in
a cinema.
The controller returns to normal
operation provided there are no
further fault messages.
Following a "Deep discharge
protection" message in the main
screen, the batteries must be test-
ed and replaced if necessary.
If a reset happens, the controller of
the station ZB-S returns to a normal
operation, if no further failure mes-
sages occur.
If the main screen displays the
message "Insulation failure" then
fault locating can be initiated with
01
this menu option.