DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Table of Contents Revisions ..........................vii Product Warranty ........................ viii Safety Notices ........................ix Keep Away from Live Circuits ..................ix RESUSCITATION ......................
Page 3
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 7.13 Final Installation Check ....................16 Operation ..........................17 Local Control Rotary Switch ..................18 Remote Control ......................18 Touch Screen Control and Display ................
Page 4
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 9.7.5 24V Indicator “D15” & “D16” ..................37 9.7.6 Control Board Relay Indicators “D11” to “D18” ............38 9.7.7 Real Time Clock ......................
Page 5
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Table of Figures Figure 1: CCR Dimensions (Trolley), Height, Length and Width..........8 Figure 2: Remote Control Using Internal Power ................10 Figure 3: Remote Control Using External Power .................
Page 6
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 36D: CCR, Door Panel, Major Replaceable Parts ............. 54 Figure 37: L-829 Menu Tree ......................56 Figure 38: Lamp Out Error ......................60 Figure 39: Service Menu.......................
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Revisions Revision Issue/Reissue Number Number Letter Description Checked Approved 219-168 Initial release 7/22/19...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Product Warranty Warranty Refer to Eaton’s Crouse-Hinds Airport Lighting Products Terms and Conditions for product specific warranty information. viii...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Safety Notices This equipment is normally used or connected to circuits that may employ voltages which are dangerous and may be fatal if accidentally contacted by operating or maintenance personnel.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Safety Symbols Danger DANGER: DANGER The hazard or unsafe practice will result in severe injury or death. Warning WARNING: WARNING The hazard or unsafe practice could result in severe injury or death.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Recommended Test Equipment and Tools There are a wide variety of tools and equipment needed to safely and correctly perform airfield lighting equipment installation and maintenance.
Page 12
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Screwdriver, straight blade, 3/32, Wera P/N 05118008004 or equal Screwdriver, straight blade, 1/8, Stanley P/N 66-112 or equal Screwdriver, straight blade, 3/16, Proto P/N 9403 or equal Screwdriver, straight blade, 5/16, Proto P/N 9406 or equal A calibrated adjustable torque screwdriver.
Page 13
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ A cable penciller for preparing ends of FAA L-824 cable for connector kits, Crouse-Hinds Airport Lighting P/N 10036-36. Cable/wire (recommend using #24-20 AWG) to connect Regulator remote control terminal block (will accept #24-12) to a control system if remote control is to be utilized.
Applicability This manual covers only the following Eaton Crouse-Hinds CCR’s: a. 4kW, 7.5kW, 10kW, 15kW, 20kW and 30kW CCRs bearing Eaton, Crouse-Hinds catalog number series 82860SGSPR-480- _ _ - _ - or 82960SGSPR-480- _ _ - _ -. Equipment Features •...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Options This CCR can be factory supplied with a Megatrac Internal earth leakage detector. FAA Classification Specification: Constant Current Regulator manufactured and qualified to FAA Advisory Circular 150/5345-10 (latest) Type: L-828 and L-829 Regulator...
Page 16
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 16.4 – 17.0 16.7 19.7 – 20.3 8.2 – 8.8 20 A 10.0 – 10.6 10.3 12.1 – 12.7 12.4 15.5 –...
The CCR Power Module (the “trolley” mounted CCR) can only be installed in an Mechanical: Eaton Crouse-Hinds part number 34296 Switchgear CCR Cabinet. The Power Module plugs into its “stab” mating half in the Switchgear CCR cabinet (when the Switchgear Main Input Cabinet circuit breaker is on, the red indicator on the door panel face for the CCR installed in the Switchgear Cabinet bay will illuminate if power is present and connection is good).
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Installation WARNING: Maintenance and troubleshooting on Constant Current Regulators IMPORTANT (CCRs) should only be performed by qualified electricians with a working knowledge of airfield lighting series circuit power.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Recommended Installation Tools See Section 5. Mechanical Installation Unpack the Constant Current Regulator, and check for any shipping damage. Install the PRO Power Switchgear CCR into a Crouse-Hinds P/N 34296 Switchgear CCR Cabinet only.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Electrical Installation CAUTION: Do not perform a megger/insulation resistance test to the series CAUTION lighting load while it is connected to the CCR. WARNING: The S-1 Cutout mounted in the CCR will aid in troubleshooting the CCR by shorting the airfield load connections together, and also...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Remote Control Connections WARNING: Incorrect wiring can cause a malfunction or damage to the control NOTICE system and may void the equipment warranty. Recheck these connections before operating.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Remote Using External Power Supply For remote operation using external voltage (10VAC to 120VAC or 24VDC to 48VDC), verify the jumper is placed on the Control Board between terminals E2 and E3 above TB1 where the remote wiring is connected.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 4: Remote via Serial Communication The display board has two RS485 ports (TB300 and TB301) for redundant communication with Crouse- Hinds ALCMS.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ SW300 DIP # ► Serial Address ▼ OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ CCR Configuration The CCR is shipped with its configuration as specified when it was ordered, but may need to be reconfigured for different application (number of steps, for example).
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Configuration Dip Switch Settings Table 2 below shows the settings configured by control board switch SW1. CAUTION: Do not change current output switch setting. 10 kW and smaller CAUTION CCRs are only available with 6.6A output current.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ L-829 Monitor Enable L-829 models are configured with L-829 monitoring active. This monitoring can be disabled by its configuration switch or via the on display setup menu (to use the on display setup menu the L-829 DIP switch must be in the ON position).
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Operation Figure 6 shows the standard Switchgear Pro Power Premium CCR controls and indicators on the front door panel (CCR control panel controls along with the circuit breaker actuator protrude through cutouts in the cabinet door), along with integral circuit breaker on/off actuator.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Local Control Rotary Switch The local control rotary switch is used to command the CCR into various brightness steps from the front panel or to place it into remote control mode to accept remote commands.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 7: Display Home Screen 8.3.1 Home Screen The home screen displays basic operating information. There are two panels, home slots 0 and 1, which can be set by the user.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 8.3.2 Main Menu The CCR Main Menu (see Figure 7), provides access to additional sub menus and informative / configuration screens.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 8.3.3 Help Menu The Help Menu provides service tips, L829 help and contact information. Figure 10: Help Menu 8.3.4 Status Menu 8.3.4.1 Status Summary Open the MAIN MENU from the home screen;...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 8.3.4.2 ALCMS Port Status Open the MAIN MENU from the home screen; select the STATUS tab, then ALCMS tab to view communication port status.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ e. COMM: Internal communication with High Voltage Unit f. MANUAL MEASURE: Trigger insulation measurement g. SELF TEST: Trigger High Voltage Unit internal test 8.3.5 View Data 8.3.5.1 Output Data View Output Voltage, Current, Power, VA, Frequency and Power Factor.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 15: Display Input Data 8.3.5.3 Operating Hours View total operating hours and step operating time. Open the MAIN MENU from the home screen. Select the VIEW DATA tab, and then select OPERATING HOURS.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 17: Display Internal Data 8.3.6 Setup Menu 8.3.6.1 CCR Name Entry Open the MAIN MENU from the home screen; select the SETUP tab, then CCR NAME tab to set the Name of the regulator.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 8.3.6.2 Set Date and Time Open the MAIN MENU from the home screen. Select the SETUP tab, then SET TIME tab to set the time and date.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 8.3.6.4 ALCMS Failsafe Open the MAIN MENU from the home screen. Select the SETUP tab, then ALCMS FAILSAFE tab to set the failsafe parameters.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 22: Insulation Test Setup c. Test Period; How often the test is performed (Hours:Minutes) d. Warn Level; Mega ohm level of resistance CCR Output to chassis ground e.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Diagnostics and Maintenance CCR Safety DANGER: DANGER Turn electrical power to the CCR at its integral circuit breaker (CB1) before opening the CCR door and attempting servicing.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ DANGER: DANGER Airfield series lighting circuits may be energized by other external sources. Prior to handling CCR output, check for the presence of voltage from output terminals to ground before working on airfield series circuit.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 3. Check all wiring connections for loose connections and tighten as necessary. See Table 7 and 4. Table 8 of Section 9.12 for hardware torque values for input/line, input/ground, equipment ground and output/load torque values.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ WARNING: The circuit cards contained in the CCR are static sensitive. Do not NOTICE remove or handle them without a static control wrist strap. Circuit boards should be stored in static sensitive bags.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 24: Power Troubleshooting Flowchart Note, LEDs can be safely viewed by powering the control board with a DC supply.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Control Board This section is not intended to give component-level troubleshooting guidance, but to document its basic functions and indicators that may be helpful in troubleshooting. The control board microprocessor (MCU) executes all basic functions of the CCR.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ COM – Common, NO – Normally Open, NC – Normally Close TB3 (see Figure 25) Table 3: TB3 Contact placement TB3 (see Figure 25) Standard L828 Standard L829...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 9.7.1 Control Board Diagnostic Indicators There are LED (Dxx) indicators associated with the major functions of the control board as shown in Figure 26.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 9.7.6 Control Board Relay Indicators “D11” to “D18” There are LED indicators associated with each of the 8 control board relays as shown in Figure 27. Each blue LED is illuminated when its associated relay is energized and the normally open contact is closed.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Display Board The Display board microprocessor (MCU) executes all the touch commands and displays the CCR data. It receives all the CCR data via CAN BUS from the main control board.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ j. Re-install cover on door over circuit boards. Close the CCR door and reapply input power. 9.8.2 Reset Display Board EEPROM Parameters In case needed, follow the steps below to reset display board EEPROM parameters.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 9.8.3 Megatrac F/O Adapter (option M) For Megatrac operation the fiber optic adaptor (34340), must be connected to J302 on the display board (see Figure 28), and a fiber optic multi-mode cable must be connected between the fiber optic adapter and the high voltage unit located on the CCR top left above the horizontal rows of capacitors (see Figure 29).
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Terminal Board The terminal board (34232) is a high voltage board that is designed to incorporate input wiring and operate the CCR contactor.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 9.11 Remote Control The remote control consists of a series of optically isolated digital input lines and an internally regulated 24VDC power supply on the control board.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 32: Remote Control Troubleshooting Flowchart Note, to read values with cabinet door closed and cover on, wires need to be connected to terminal block positions that will be checked and then routed to the outside of the cabinet interior.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 33: Standard Wiring Diagram, Complete (See Figure 34 & Figure 35 for enlarged halves of this diagram)
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 34: Standard Wiring Diagram, Part A...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 35: Standard Wiring Diagram, Part B...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 9.13 Recommended CCR Spare Parts The number of recommended parts depends on the quantity of Switchgear PRO Power CCRs present at your airfield.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ TRANSFORMER (T1), REF S-1 CUTOUT, P/N 30775 CABLES NOT INCLUDED OPTION "M" HIGH VOLTAGE UNIT, P/N T9006-93-13-00 POWER CABLE FOR HIGH VOLTAGE UNIT (NOT SHOWN), P/N1500101-1 FIBER OPTIC CABLES (NOT SHOWN), P/N 10056-2287...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ MAIN CIRCUIT CARD, RED COLOR BUS ENGAGED INDICATOR LIGHT, REF P/N 34229 TOUCH SCREEN W/INTEGRAL CIRCUIT CARD, P/N 10047-3176 MAIN CIRCUIT CARD FUSES F1 &...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ L-829 Monitor; Use and Display L-829 monitoring provides sensing and alarms for the following FAA specified internal and external faults: 1) Loss of input power to the CCR.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 37: L-829 Menu Tree 10.1 L-829 Setup and Calibration WARNING: Before entering setup data for L-829 functions, disable both LAMP IMPORTANT COUNT MODE and PERCENT MODE.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 3) Lamps must be incandescent types. LED fixtures cannot be monitored accurately in lamp count mode. 4) No film disc cut-outs may be used The lamp out alarm has two alarm levels.
Page 71
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Press the POWER CALIBRATION START button. The button will change from START to ACTIVE while the CCR automatically detects and saves the field circuit power profile at the two maximum brightness steps.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Press the LAMP CALIBRATION START button. The button will change from START to ACTIVE while the CCR automatically detects and saves the field circuit power profile at the two maximum brightness steps.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 38: Lamp Out Error After the additional number of user selected lamps has failed, “L829 ALARM” will reappear on the display.
Service menu should only be accessed by certified Crouse-Hinds Engineer or if instructed by Crouse- Hinds support team. Figure 39 shows the Service menu tree. WARNING: Please read this manual carefully and contact Eaton Crouse-Hinds technical support before accessing the service menu. Some IMPORTANT...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ Figure 39: Service Menu DANGER: Turn electrical power to the Constant Current Regulator (CCR) at its integral circuit breaker before enabling the service menu per DANGER this section or if opening the CCR door.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 11.1 Service menu DIP switch settings a. After verifying the CCR is de-energized and locked, open the CCR front door and locate SW1 on the main control board, see Figure 25 located on the door after the cover is removed.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ 11.2 Shorting the CCR Output Make sure the CCR output is shorted (as described below) before starting the calibration procedure or performing any of the overcurrent tests.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ as reasonably close as you can get within a few hundredths of an Amp of the nominal 6.60A or 20A value we are aiming for. Note 0.01 = one hundredth. Typical results readings are 6.58 - 6.62 Amps or 19.98 –...
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ WARNING: These tests should only be performed by a Crouse-Hinds certified engineer. Please contact Crouse-Hinds support for additional IMPORTANT information.
PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ WARNING: These setting should only be adjusted by an Eaton Crouse-Hinds IMPORTANT certified engineer for specific field condition. Please contact Crouse- Hinds support for additional information.
DOCUMENT 1222 REV. A Instruction Manual PRO Power Switchgear Constant Current Regulator, FAA L-828/L-829 Series 82_SGSPR-480- _ _ - _ - _ DANGER: Turn electrical power to the Constant Current Regulator (CCR) at its integral circuit breaker before opening the CCR door. Shut DANGER OFF “External”...
Series 82_SGSPR-480- _ _ - _ - _ Maintenance Services Eaton Crouse-Hinds Airport Lighting has been performing services on CCRs for the past 40 years with currently over 100 years of accumulated experience. We offer premium service to our customers with the availability of our CCR Testing Program.